of delay will start. The second period can be programmed up to 3 minutes. At the end
of the second delay period, if fire alarm is not cleared, NACs will be activated.
If the second alarm occurs during any delay period, the delay will stop and NACs
and/or control modules will be immediately activated.
PAS does not affect waterflow indicators and supervisory devices.
Action of PAS BYPASS devices will disable PAS until they reset. The panel will
transfer from PAS condition to alarm condition immediately by pressing a pull station
during PAS delay time. A pull station shall be installed next to the FACP.
4.10 Walk Test
Walk test is a feature which allows one person to test the fire alarm system. During
audible walk test, the NACs will output for a moment and record the test information.
During silence walk test, the NACs will not output, but only record the test information.
Disabled devices will not be activated during walk test.
Alarm test: During audible walk test, each new alarm will activate the NACs and
associated modules for 3~4 seconds, the walk test of these devices shall be set to ON.
The LCD will display the alarm events, which will be marked with the word
walk test
to
distinguish with normal events. If there are no new messages in 30 minutes, the FACP
exits walk test status. During walk test, if real fire or fault happens, the LCD will clear walk
test message and show the real one.
4.11 Read Status
In the screen shown in Fig. 3-1, selecting
“1. Read Status” can view history records,
device information, E&C, network FACPs and disabled devices, as shown in Fig. 4-5.
Fig. 4-5
4.11.1 View History
Selecting
“1. View History” in the screen of Fig. 4-5 can view history records, as shown in
Fig. 4-6.
*Read Status*
1.
View History
2.
System Point
3.
Event & Command
4.
Network FACP
5.
Disable Point