GST-M200 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 39
Fig. 4-4
Description:
The first line:
“ACTIVE SUPERVISORY” means supervisory message.
The second line:
“001” is the number of the message and “040” is the number of total
messages.
The third line:
“SUPERVISORY” is the device type and “C001’ is device address.
The fourth line:
“16:34 0112” is the time the event occurs in the sequence of Hour,
Minute, Day, Mouth;
“Z001” is the zone number.
The fifth and sixth lines: Device description, maximum 32 characters.
4.8 Coded Operation
The NAC circuits on the control panel loop interface board can be programmed for coded
operation. The available pulse rates which can be programmed for coded operation are as
follows:
Steady - a continuous output with no coding.
Temporal - ½ second on, ½ second off, ½ second on, ½ second off, ½ second on,1½
second off.
4.9 Positive Alarm Sequence
PAS (Positive Alarm Sequence) procedure: When a detector alarms, sound indication of
the panel can be started immediately and PAS Relay devices are activated. NACs will not
be activated within 15 seconds. Pressing
ALARM SILENCE
or
ACK/STEP
key within this
period, local sound will be silenced and the second period of delay will start. The second
period can be programmed up to 3 minutes. At the end of the second delay period, if fire
alarm is not cleared, NACs will be activated. If the second alarm occurs during any delay
period, the delay will stop and NACs and/or control modules will be immediately activated.
PAS will activate the following:
Immediately start sound indication.
PAS relay devices are activated.
NACs will not be activated within 15 seconds. Pressing
ALARM SILENCE
or
ACK/STEP
key within this period, local sound will be silenced and the second period
ACTIVE SUPERVISORY
001 0f 040
SUPERVISORY
C001
16:34 0112 Z001
description
:
(32 char, 2line)