GST-M200 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 17
2.6 Signaling Line Circuits (SLC)
IN +
IN -
OUT -
OUT +
LO
O
P-
IS
O
ZO2
ZO1
Z1
Z2
LO
O
P-
IS
O
ZO1
ZO2
Z2
Z1
Fig. 2-7
Connection of SLC:
C-9503 / C-M9503 / GST-LD-8322 Loop Isolator must be connected in SLC loop, each
administrating a maximum of 30 addressable devices. The SLC can have at most 240
devices. Compatible devices are I-9102(UL) / JTY-GD-G3 Intelligent Photoelectric Smoke
Detector, I-9103(UL) / JTW-ZCD-G3N Intelligent Rate of Rise and Fixed Temperature
Heat Detector, I-M9300 / GST-LD-8300 Addressable Input Module, and I-M9301 /
GST-LD-8301 Addressable Output Module.
2.7 UL Power-limited Wiring Requirements
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet.
All power-
limited circuit wiring must remain at least 0.25” (6.35mm) away from any
nonpower-limited circuit wiring and nonpower-limited circuit wiring must enter and exit the
cabinet through different knockouts and/or conduits. A typical wiring diagram for the
GST-M200 is shown below.