GST-M200 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 36
appropriate section in this manual.
Fig. 4-1
Description:
The first line: Displaying the contents of Banner.
The second line: Displaying current date by day-month-year order and software
version of the FACP.
The third line: Displaying
SYSTEM ALL NORMAL
indication.
Under normal operation, the FACP executes the following tasks regularly.
Monitors AC input voltage and battery voltage.
Monitors and reports status of SLC loop and the control panel.
Polls all devices on the SLC loop and flash each device LED while checking for valid
replies, alarms, troubles, etc.
Scans control panel keypad for key presses.
Performs self-test for all SLC devices
4.4 Trouble Operation
With no alarms in the system, the detection of a trouble will cause the following:
The speaker of the panel pulses 1 second On and 1 second Off.
The system
TROUBLE
LED lights.
Devices defined as
Trouble Relay
activate.
The word
TROUBLE
with device type, address and trouble description will appear on
the LCD.
Write history buffer.
For messages with separate LED indication, LED and LCD indicate at the same time.
But
SYSTEM FAULT
only has LED indication.
Display for automatically reset troubles can be cleared by itself, and return to normal
state.
SLC Line Fault
is latching signal that cannot automatically reset. It has to be reset
manually.
Note that specific troubles will initiate additional actions. For example, loss of AC power
Display contents of Banner
16/09-09 V***
SYSTEM ALL NORMAL