GST-M200 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 7
which must comply with the actual supply power. When X2 is shorted,
the FACP should work under 120VAC. When X2 is disconnected, the
FACP should work under 220VAC.
Battery (Sealed Lead Acid Only) - (BAT+, BAT-)
Rated voltage: 24VDC, Maximum voltage 27VDC
Maximum charging current: 1.10A
Float charging voltage: 27.5VDC
Type of suitable battery: 24V / 20Ah
Derating feature: 15 percent of full capacity.
SLC(Signaling Line Circuit) LOOP - XT4, XT6
24VDC nominal, 28VDC maximum
Maximum length is 4000ft.
Maximum loop current is 0.2A(short circuit)
. See also Section 7 for relationship
between max. wire length and loop current
.
NAC (Notification Appliance Circuit) - XT8 (NAC1) & XT7 (NAC2)
Power-limited, supervised, and regulated circuit.
Maximum voltage drop in wiring: 2.0VDC
Nominal operating voltage: 24VDC
Current-limit: electronic, power-limited circuit.
Rated signaling current per circuit: 0.001A (see Fig. 1-1)
Maximum signaling current per circuit: 1.2A (see Fig. 1-1)
End-of-line resistor: 4.7
kOhm
for Style Y (Class B) NAC
Three Fixed Relay: XT13 (Supervisory), XT11 (Alarm) & XT12 (Fault) - For common
use.
Contact rating: 2.0A @ 30VDC (resistive).
Refer to Fig. 2-5 for information on power-limited relay circuit wiring.
24VDC: XT10
Power-limited, supervised, and regulated circuit.
Maximum voltage drop in wiring: 2.0VDC
Nominal operating voltage: 24VDC
Current-limit: fuseless, electronic, power-limited circuit.
Standby rating current per circuit: 0.05A
Maximum signaling current per circuit: 0.75A
EIA-485: XT1 (For Future Use)
Auxiliary output: Terminal 1 (A) and Terminal 2 (B) - no connection.
Current Availability
The following figure illustrates the maximum current available from the FACP.