Smart Climate 310 rev. 03 75
6. Press
Adjust
and then use the arrow keys to set the status
of each temperature probe.
7. Select "On" to assign a probe to the air inlet.
Compensating for Static Pressure on the Inlet
Opening
Compensation can be used to ensure uniformity in the static
pressure level in the room.
The static pressure compensation allows opening or closing the air
inlet further when the static pressure level is out of range. When it
used, the compensation applies to all air inlets (regular & 0-10V air
inlets). The compensation can be deactivated for all air inlets
individually by setting its value to Off.
When the static pressure level exceeds the normal range (above
the Hi Pressure Set point or below the Lo Pressure Set Point), the
controller waits for the
Wind Effect Delay
to make sure this unusual
pressure condition is not temporary.
If the pressure is still out of range after this delay has elapsed, the
inlet SP Compensation (%) is applied on the opening of the inlet: it
closes further by its SP compensation value (%) when the pressure
level is too low [
point A
on the graphic] or opens further by its SP
compensation value (%) when the pressure level is too high [
point
C
on the graphic].
Содержание Smart Climate 310
Страница 1: ...Smart Climate 310 User s Guide 895 00676 REV 04 890 00582 REV 03...
Страница 12: ...12 Smart Climate 310 rev 03 Internal Switches Internal switches are located inside the auxiliary module...
Страница 96: ...96 Smart Climate 310 rev 03 Probe Assignment...
Страница 97: ...Smart Climate 310 rev 03 97 User Setup Menu...
Страница 98: ...98 Smart Climate 310 rev 03...
Страница 101: ...Smart Climate 310 rev 03 101 3 Press on the card and make it clip to the main board...
Страница 102: ...102 Smart Climate 310 rev 03...