68 Smart Climate 310 rev. 03
For each degree above or below the average temperature, the inlet
will open or close using the compensation value assigned by the
user. For example, if the compensation value is set to 2%/°F and
the inlet's probes read 3 °F above the average controller
temperature, the inlet will open 6% to help decrease the
temperature in that zone.
Inlets in Minimum Ventilation
During the off-time part of the minimum ventilation cycle, inlets
open to Step 0. During the on-time part of the cycle, they open to
Step 1. But, if the option Inlet Follow Minimum Speed? is set to
“Yes”, the controller will modulate the inlets’ opening between Step
1 and Step 1Hi depending on the minimum speed of the variable
fan as shown below.