Smart Climate 310 rev. 03 63
Adjusting the Maximum and Stop T° for the 0-10V
Heating Output
The
maximum temperature
is the temperature at which the 0-10V
heating output reaches its full intensity. It ranges from 0.5 to 20°F
(0.3°C to 11.1°C) below its minimum temperature (see previous
diagram). The
stop temperature
is the temperature above which
the output is deactivated. It can be set from 0.5 to 20°F (0.3 to
11.1°C) above its minimum temperature.
To set the maximum and stop temperatures for the 0-10V heating
output, proceed as follows:
1. Press
0-10v Output
.
Make sure the 0-10V output is configured in heating mode in the
USER SETUP.
2. Press the down-arrow key in order to select the
Max t°
/ Stop At
display.
3. Press
Adjust
. The maximum temperature flashes on
the display.
4. Use the arrow keys to set it to the desired value.
5. Press
Adjust
once again, the stop temperature flashes
on the display.
6. Use the arrow keys to set it to the desired value.