Over-Opening Stage
A supplementary stage can be calibrated in order to continue
opening the air inlet beyond the last temperature of the controller's
ventilation stages.
This supplementary stage is used to direct the airflow more
efficiently during periods of warm weather.
You must specify the maximum inlet opening and the number of
degrees over the last ventilation stage at which this opening must
be reached.
NOTE
: Over-opening stage only applies to air inlets and not to
chimney dampers.
The inlet can reach this maximum opening in 2 different ways:
Progressive Mode:
The controller gradually
opens or closes the panels in a linear
fashion as the room temperature rises above the last reference
point temperature. The inlet reaches its maximum opening at the
"temperature of the last
reference point + #of degrees to max.
opening".