Figure 5-16
Connecting a PE cable
•
The PE point at the AC output port is used only as a PE equipotential point,
and cannot be substituted for the PE point on the enclosure.
•
To enhance the corrosion resistance of a ground terminal, apply silica gel or
paint around the terminal after connecting the ground cable.
•
Earth fault Alarm: There is the earth fault alarm as the additional detection.
When this alarm is detected, the system buzzer will sound and the red
indicator light will flash.
Impedance of the PV arrays is less than 30KΏ.
External connection between PIN1 and PIN2 or RELAY2 must be within the
range of 300V 2A
Installing the Cable between the Main Control Box and
Battery Box
Before use, the ba
ttery box’s DC cables and communication cables need
to be connected to the main control box.
Do not connect the negative plug (black) of battery pack #1 until the battery box is
connected to the inverter.
Procedure
Step 1
Install the communication cable (Can cable). The communication cable is
pre-installed in the battery box, to locate the cable to be connected to the
RJ45 connector.
Step 2
Insert one RJ45 side of the cable into the BMS port of the control box.
Ensure you select the correct specification cables for installation, otherwise the power
will make the cable hot or burnt, and can result in serious injury or death.
Step 3
Connect one side of the battery connect wire to the position shown in
Figure 5-17.
Step 4
Connect the positive side of the battery connect wire to the positive side
of the battery.
Step 5
Connect the negative side of the battery connect wire to the negative side
of the battery.