Powering on the System
Before turning on the AC switch between the Tesseract 5K14 and the
power grid, check that the AC voltage on the power grid side of the AC
switch is within the specified range.
•
If the DC is on and the AC is off, the Tesseract 5K14 reports a Grid Failure alarm.
The Tesseract 5K14 starts normally only after the fault is rectified.
•
The Tesseract 5K14 will recover automatically when it detects the grid recovered.
When the AC is off, the Tesseract 5K14 will shut off from the grid and provide
power to EPS load automatically
•
If the AC is on and the battery is off, the Tesseract 5K14 reports a Battery
Abnormal alarm.
•
If the Tesseract 5K14 is connected to the battery, after turning on the AC switch:
•
If the DC switch is turned on within 1 minute, the Tesseract 5K14 will run properly
in grid-tied mode.
•
If the DC switch is not turned on within 1 minute, the Tesseract 5K14 will enter
the night-time grid-tied mode. Then, after the DC switch is turned on, the
Tesseract 5K14 will shut down and then restart to run in grid-tied mode.
First Start
Step 1
Confirm that battery switch (Figure 5-8) is off.
Step 2
Connect the #1 battery pack negative plug (Figure 5-5).
Step 3
Confirm that the Battery ON/OFF button LED (Figure 5-2) is lit.
Step 4
Turn on battery switch (Figure 5-8).
Step 5
Start the procedure.
Procedure
Step 1
Turn on the AC switch between the Tesseract 5K14 and the power grid.
Step 2
Turn on the DC switch for PV (Figure 5-8
“A”).
Step 3
Turn on the DC switch between the PV string and the Tesseract 5K14 if
there is any.
Step 4
Turn on the DC switch at the bottom of the Tesseract 5K14.
Step 5
Observe the LEDs to check the Tesseract 5K14 operating status.