Reactive power control, Reactive standard curve cosφ=f (P)
For VDE ARN 4105, curve cos φ = f(P) should refer to curve A. default values of setting
are as shown in curve A.
For E 8001, curve cos φ = f(P) should refer to curve B. default values of setting are as
shown in curve B.
For CEI 0-21, default value of PFLockInPoint is 1.05, when Vac > 1.05Vn, and Pac> 0.2
Pn, curve cos φ = f(P) should refer to curve C. Default value of PFLockOutPoint is 0.98,
when Vac < 0.98 Vn, cos φ = f(P) will exit curve C.