5.3.2 Installing the AC Input/Output Power Cable (Grid)
Do not connect any load between the Tesseract 5K14 and the AC switch.
Procedure
Step 1
Check the grid voltage and compare with the permissible voltage range
(see technical data).
Step 2
Disconnect the circuit-breaker from all the phases and secure against
reconnection.
Trip the PE wire to 55 mm and all other wires to 52.5 mm. Use the
crimping pliers to trip 12 mm of insulation from all wire ends as shown in
Figure 5-11.
Figure 5-11
Stripped length
Step 3
Connect the AC cables into the “GRID” connection as shown in Figure 5-
12.
Figure 5-12
AC cable connection