If the external AC switch can perform earth leakage protection, the rated leakage
action current should be greater than or equal to 100 mA.
•
If multiple Tesseract 5K14s connect to the general residual current device (RCD)
through their respective external AC switches, the rated leakage action current of
the general RCD should be greater than or equal to the number of Tesseract
5K14s multiplied by 100 mA.
•
A knife switch cannot be used as an AC switch.
Table 5-4
Cable descriptions
No.
Cable
Type
Conductor
Cross-
sectional
Area Range
(mm
²
)
Outer
Diameter
(mm)
Source
1
DC input
power
cable
Standard PV cable in
the industry
Recommended model:
PV1-F
6
4.5
–7.8
Prepared
by the
customer
2
Signal
cable
Four-core outdoor
shielded twisted pair
1
4
–11
Prepared
by the
customer
3
AC output
power
cable
Not using the PE
equipotential point at the
AC output port: two-core
(L and N) outdoor
copper cable
Using the PE
equipotential point at the
AC output port: three-
core (L, N, and PE)
outdoor copper cable
6
10
–21
Prepared
by the
customer
4
PE cable
Single-core outdoor
copper cable with an M6
OT terminal
10
N/A
Prepared
by the
customer