INSTALLATION
Gentherm Global Power Technologies
Page 30
5.6.3
Propane/Natural Gas Supply Considerations
If remote Propane/LPG gas supply system is used, consider the following:
Location:
Propane/LPG tanks and cylinders must be located outdoors in a well-ventilated
area, at least 3 meters (10 ft) from the TEG unless directed otherwise by the local authority
having jurisdiction.
Mounting:
Each tank or cylinder must be set on a firm, level, water proof base, located on
consolidated ground at grade level. The base must extend at least 300mm (1 ft) from all
sides of the tank or cylinder, must be designed to support the weight of the tank or cylinder
and is subject to approval by the local authority having jurisdiction.
Connection:
Tanks and cylinders are to be equipped with flexible connections to offset any
movement affecting the piping or tubing.
5.7
CONNECTING CUSTOMER LOAD
Figure 14 - Wiring Diagram P-5100 for 12 or 24 V