INSTALLATION
Gentherm Global Power Technologies
Page 27
5.5
MOUNTING
Mount the TEG to a firm and stable base, using 1/4-20 bolts of material suitable for the
environment. See Figure 11 for mounting hole locations. The base must be level and sturdy
enough to support the 83 kg (183 lb.) mass of the TEG.
CAUTION!
Operation of the TEG in locations where cooling air
flow may be obstructed will cause overheating of the
TEG. Allow a minimum of 150 mm (6 in.) clearance
under the cooling fins and 900 mm (3 ft.) above the
top of the fin duct. Locate the TEG to avoid flooding
interfering with the flow of cooling air.
Figure 11
–
Model P-5100 Mounting Dimensions