Section 7 A/C System Faults Check & Troubleshooting
I. A/C System Faults Check
Inspection shall be made to isolate the fault area and its cause when the fault of A/C system occurs, and then
specific service could be performed. Inspect the whole system before re-using A/C system after a long term
of storage.
First step is initial inspection by direct "see, listen and touch". Test the system with the leak detector if
necessary.
1. Check the Refrigeration System
Under the normal condition, the low pressure pipeline of the A/C refrigeration system takes on a status of low
temperature and the high pressure pipeline takes on a status of high temperature, see Figure 16. Based on
this rule, you can arrive at the initial judgement about the fault area and its cause by touching the refrigeration
system pipeline and elements to feel the surface temperature with your hand.
1
High pressure area: compressor outlet
condenser receiver/drier
expansion valve
inlet, its temperature change trend is from warm
to hot. If the temperature change is not this trend,
but instead some part is extremely hot (e.g.
condenser surface), it indcates that the part is
faulty and the radiation is not good; if some part is
extremely cold (e.g. receiver/drier) or there is frost
(e.g. at expansion valve inlet), it indicates that the
part is faulty and the pipe may be blocked.
2
Low pressure area: expansion valve outlet
evaporator
compressor inlet, its temperature
change trend is from cool to cold, If the
temperature change is not this trend, it indcates that the part is faulty.
3
Compressor: compressor inlet and outlet high & low side shall have apparent feel of temperature difference,
if there is no temperature difference, it indicates that there is leakage in the system and the refrigerant
has leaked.
2. Check the Leakage Area
1
Observe all connecting areas of the refrigeration system or condenser surface for oil stain, if there is oil
stain, it indicates that the the refrigerant is leaking (refrigerant and freezing oil leak simultaneously,
refrigerant volatilize after leakage and leave the freezing oil remained to be oil stain).
2
Apply the soap water to the connecting area, if soap bubble occurs, it indicates that there is leakage.
3
Check with instrument, the common instrument is halogen leak detector. When using the halogen leak
detector for check, the key is the propane flame color depending on which the judgement is made. When
there is no leakage, the flame color remains unchanged, when there is a little leakage, the flame is
greenish, when there is large leakage, the flame is bluish or purple.
Cool
Cold
Hot
Warm
Expension
Valve
Compressor
Evaporator
Condenser
Gas
Gas
Liquid
Liquid
Low Pressure
High Pressure
Figure 16 A/C System Process
→
→
→
→
Содержание CK MR479Q 2007
Страница 1: ......
Страница 52: ...45 Section 4 Fuel Pump Replacement Figure 102 ...
Страница 57: ...50 Chapter 5 Exhaust System MR7131A MR7151A MR7161A Component1 Figure 116 ...
Страница 63: ...56 Chapter 7 Clutch MR7131A MR7151A MR7161A Component 1 Hydraulic Manipulation Figure 131 ...
Страница 66: ...59 Chapter 8 Maunal Transaxle Assembly MR7131A MR7151A MR7161A Component 1 Figure 139 ...
Страница 143: ...136 Section 4 Power Steering Gear Retaining Device Components Front Cowl Panel Assembly Cotter Pin Cotter Pin ...
Страница 208: ...201 High Mounted Stop Lamp LH Rear Combined Lamp Rear Trunk Lamp Switch License Plate Lamp RH rear Combined Lamp ...
Страница 246: ...239 Tweeter Antenna Cable Antenna Assembly Front Speaker Assembly Rear Speaker Assembly ...
Страница 300: ...293 8 Remove the whole HECU from the bracket ABS HECU Assembly ABS HECU Brake Pipe Removal Schematic ...
Страница 387: ...380 5 24 1 2 3 4 Figure 5 24 COWL 1 Cowl 2 Heat Insulating Protecting Board 3 Front Cross Member 4 Heat Insulating Pad ...