Programming Site Data
4-39
April 2009
Entering the Analog Output
The Analog Output option enables you to enter information to set
up output parameters. To enter the option, scroll to the Analog
Output entry on the Program Menu and press
[ENTER]
. The screen
appears similar to Figure 4-18 below. To step through each
parameter, press the [
T
] key. Refer to Figure A-6 on page A-6 of
Appendix A,
Menu Maps.
Figure 4-18: The Analog Output Window
1.
The first prompt enables you to select a range to send a current
signal to a recording device.
a.
Press
[ENTER]
to open the drop-down menu.
b.
Scroll to the desired output from three choices: Off,
0-20 mA, and 4-20 mA.
c.
Press
[ENTER]
to confirm your selection.
Note:
If you select “Off,” you cannot access any other
parameters in this option.
Analog Output
Cancel
OK
Function
Data Source
Zero
On Error
0-20 mA
Velocity
Span
Hold Last Value
0
m/s
25.5