Chapter 5. Ethernet Global Data
72
PACSystems* RX7i & RX3i TCP/IP Ethernet Communications User Manual
GFK-2224Q
Valid Memory Types for Ethernet Global Data
The PLC memory types listed below can be included in EGD exchanges.
Memory Type
Description
P-Producer
C-Consumer
%R
Register memory in word mode
P/C
%W
Word memory in word mode
P/C
%AI
Analog input memory in word mode
P/C
%AQ
Analog output memory in word mode
P/C
%I
Discrete input memory in byte mode
P/C
%Q
Discrete output memory in byte mode
P/C
%T
Discrete temporary memory in byte mode
P/C
%M
Discrete momentary memory in byte mode
P/C
%SA
Discrete system memory group A in byte mode
P/C
%SB
Discrete system memory group B in byte mode
P/C
%SC
Discrete system memory group C in byte mode
P/C
%S
Discrete system memory in byte mode
P
%G
Discrete global data table in byte mode
P/C
Symbolic Variables
Symbolic variables
P/C
Discrete point references such as %I or %Q are configured as Byte-Array, Word-Array, or Dword-Array
variables. That means a variable with discrete point references must be defined in blocks of 8 points if it is
defined as a Byte-Array, 16 points if Word-Array, and 32 points if Dword-Array. Discrete memory must be byte-
aligned.
Boolean type and Boolean-Array variables are not allowed.
To use a symbolic variable in an EGD exchange, it must exist in the Variables definition for the target. To add it
to an exchange, double click the Variable field to open a selection dialog box.
Figure 35: Adding Symbolic Reference to Ethernet Global Data Exchange
Planning Exchanges
It is possible to configure more Ethernet Global Data than a PLC can transfer (especially on 10Mbit networks). If
high levels of consumer timeouts occur in some or all of the consumed exchanges, the EGD load can be
reduced by:
▪
Increasing the production period (especially if the period is more frequent than double the minimum time in
which the data is needed).
▪
Defining fewer exchanges, each with more data.
Содержание PACSystems RX7i
Страница 45: ......
Страница 54: ...Chapter 4 Configuration GFK 2224Q January 2017 41 Figure 18 CPE400 Advanced Ethernet Configuration LAN1 LAN 2 ...
Страница 80: ...Chapter 4 Configuration GFK 2224Q January 2017 67 ...
Страница 81: ......
Страница 122: ...Chapter 6 Programming EGD Commands GFK 2224Q January 2017 109 ...
Страница 142: ...Chapter 7 Programming SRTP Channel Commands GFK 2224Q January 2017 129 Figure 51 Sample Ladder Logic for COMMREQ ...
Страница 147: ......
Страница 193: ...Chapter 10 OPC UA Server 180 PACSystems RX7i RX3i TCP IP Ethernet Communications User Manual GFK 2224Q Example ...
Страница 202: ...Chapter 10 OPC UA Server GFK 2224Q January 2017 189 Figure 73 Machine Edition Online Command to Set Passwords ...
Страница 211: ......
Страница 253: ...Chapter 12 Diagnostics 240 PACSystems RX7i RX3i TCP IP Ethernet Communications User Manual GFK 2224Q ...
Страница 262: ...Chapter 13 Network Administration GFK 2224Q January 2017 249 ...
Страница 263: ......