Chapter 10. OPC UA Server
GFK-2224Q
January 2017
177
OPC UA Server – Service Request – CLEAR
This function clears the configuration files and certificates used by the OPC UA Server on the controller.
Note:
This request can only be successfully performed when the server is stopped.
Parameters for the CLEAR function service request are:
Parameter
Summary
Data Direction (LD
perspective)
16#0001
OPC UA protocol
IN
16#0002
CLEAR request
IN
If the SVC_REQ does not pass power, the operation did not complete.
Example: