Chapter 9. Modbus/TCP Client
GFK-2224Q
January 2017
155
Command 3004, Example 1 – Set Single Register
Write one register from %AI10 to register address 200 in the remote Modbus/TCP server. Return the COMMREQ
Status word to %R10. Use channel 6, a channel previously opened with the Open Modbus/TCP Client
Connection COMMREQ.
Dec (Hex)
Word 1
00008 (0008)
Length of Channel command Data Block
Word 2
00000 (0000)
Always 0 (no-wait mode request)
Word 3
00008 (0008)
Memory type of CRS word (%R)
Word 4
00009 (0009)
CRS word address minus 1 (%R10)
Word 5
00000 (0000)
Reserved
Word 6
00000 (0000)
Reserved
Word 7
03004 (0BBC)
Write to a Modbus/TCP Device
Word 8
00006 (0006)
Channel number (6)
Word 9
00006 (0006)
Modbus Function Code – Write Single Register
Word 10
00010 (000A)
Local PLC Memory Type
Word 11
00010 (000A)
Local PLC Starting Address
Word 12
00200 (00C8)
Address in the Remote Device
Word 13
00001 (0001)
Number of Registers in the Remote Device
Word 14
00001 (0001)
Unit Identifier
(Word 7) Channel Command Number:
Word 7 identifies the COMMREQ as a Write Data to remote
Modbus/TCP device.
(Word 8) Channel Number:
Word 8 identifies the channel number previously allocated for communication with
the remote Modbus/TCP server.
(Word 9) Modbus Function Code:
Word 9 specifies Function Code 6, Write Single Register.
(Word 10) Local PLC Memory Type:
Words 10–11 specify the location in the local PLC from where the Ethernet
interface will get the data to be written to the remote PLC. Valid values for Word 10 are listed on page 150.
(Word 11) Local PLC Starting Address:
Word 11 determines the starting address in the local PLC from which
the data is to be written. The value entered is the offset (1-based) from the beginning of PLC memory for the
memory type and mode specified in Word 10. This offset will be either in bits, bytes, or words depending on the
mode specified. Valid ranges of values depend on the PLC’s memory ranges.
(Word 12) Remote Device Address:
specifies the destination register in the remote device.
(Word 13) Number Registers in Remote Device:
Word 13 specifies the quantity of registers to write to the
remote device. For Function Code 6, Write Single Register this must be set to 1.
(Word 14) Unit Identifier:
This field is typically used by Ethernet to Serial bridges to specify the address of a
Modbus Slave on a multi-drop link. The Modbus/TCP Unit Identifier is a special control code used in a
Modbus/TCP message block.
Содержание PACSystems RX7i
Страница 45: ......
Страница 54: ...Chapter 4 Configuration GFK 2224Q January 2017 41 Figure 18 CPE400 Advanced Ethernet Configuration LAN1 LAN 2 ...
Страница 80: ...Chapter 4 Configuration GFK 2224Q January 2017 67 ...
Страница 81: ......
Страница 122: ...Chapter 6 Programming EGD Commands GFK 2224Q January 2017 109 ...
Страница 142: ...Chapter 7 Programming SRTP Channel Commands GFK 2224Q January 2017 129 Figure 51 Sample Ladder Logic for COMMREQ ...
Страница 147: ......
Страница 193: ...Chapter 10 OPC UA Server 180 PACSystems RX7i RX3i TCP IP Ethernet Communications User Manual GFK 2224Q Example ...
Страница 202: ...Chapter 10 OPC UA Server GFK 2224Q January 2017 189 Figure 73 Machine Edition Online Command to Set Passwords ...
Страница 211: ......
Страница 253: ...Chapter 12 Diagnostics 240 PACSystems RX7i RX3i TCP IP Ethernet Communications User Manual GFK 2224Q ...
Страница 262: ...Chapter 13 Network Administration GFK 2224Q January 2017 249 ...
Страница 263: ......