Chapter 4. Configuration
66
PACSystems* RX7i & RX3i TCP/IP Ethernet Communications User Manual
GFK-2224Q
Selective Consumption
Not all data ranges within a produced exchange need to be consumed by each PLC. For example, a producer is
producing an exchange consisting of a 4-byte floating point value, followed by a 2-byte integer, followed by a
2-byte analog value. If the consuming PLC wants to consume only the analog value and place it into %AI003,
the consumer might be configured as shown below.
Offset Variable
Ref Address
Ignore Length Type
Description
0.0
Ignore
True
6
Byte
Ignore float and integer
6.0
Var01
%AI0003
1
WORD
Note that where EGD signatures are not used the total length of the exchange must be the same in producer
and consumer, even if the consumer is ignoring a portion of the exchange. Failure to configure any ignored
bytes in the consumed exchange will result in exchange exception log and fault table entries, error status in the
exchange status data, and no data being transferred for the exchange.
Содержание PACSystems RX7i
Страница 45: ......
Страница 54: ...Chapter 4 Configuration GFK 2224Q January 2017 41 Figure 18 CPE400 Advanced Ethernet Configuration LAN1 LAN 2 ...
Страница 80: ...Chapter 4 Configuration GFK 2224Q January 2017 67 ...
Страница 81: ......
Страница 122: ...Chapter 6 Programming EGD Commands GFK 2224Q January 2017 109 ...
Страница 142: ...Chapter 7 Programming SRTP Channel Commands GFK 2224Q January 2017 129 Figure 51 Sample Ladder Logic for COMMREQ ...
Страница 147: ......
Страница 193: ...Chapter 10 OPC UA Server 180 PACSystems RX7i RX3i TCP IP Ethernet Communications User Manual GFK 2224Q Example ...
Страница 202: ...Chapter 10 OPC UA Server GFK 2224Q January 2017 189 Figure 73 Machine Edition Online Command to Set Passwords ...
Страница 211: ......
Страница 253: ...Chapter 12 Diagnostics 240 PACSystems RX7i RX3i TCP IP Ethernet Communications User Manual GFK 2224Q ...
Страница 262: ...Chapter 13 Network Administration GFK 2224Q January 2017 249 ...
Страница 263: ......