Chapter 12. Diagnostics
212
PACSystems* RX7i & RX3i TCP/IP Ethernet Communications User Manual
GFK-2224Q
Blink
Code
Description
Blink Code Description
0x39
Instruction cache TLB miss exception
0x78
Boot: Unexpected Restart pushbutton
interrupt
0x41
BSP startup error
12.5
Controller Fault Table
Most error conditions involving the Ethernet interface generate faults in the Controller Fault table. The table on
the next two pages lists Ethernet interface faults and corrective actions.
To access the details of a Controller Fault Table entry, double-click the Fault Table entry and the details are
displayed as “fault extra data”. Refer to Online Help in the PLC programming software for more information.
An example of the fault extra data is shown below:
Figure 89: Fault Extra Data Example
For Ethernet Interfaces the leftmost 14 digits of fault extra data (underlined in the example above) show the
corresponding log Events (2 digits) and Entries 2, 3, and 4 (in that order, 4 digits each).
The example above is reporting
▪
an Event 16,
▪
Entry 2=6,
▪
Entry 3=3, and
▪
Entry 4=5.
This information can be used to refer directly to detailed fault descriptions included in the Exception Log Event
tables in GFK-2225,
TCP/IP Ethernet Communications for PACSystems Station Manager Manual.
(In that
document, refer to Appendix B, Exception Log Events.)
Controller Fault Table Descriptions
Controller Fault
User Action
Backplane communications with
controller fault; lost request
Check to make sure that the logic application is not sending COMMREQs
faster than the Ethernet Interface can process them. Reduce the rate at
which the application is sending COMMREQs to the Ethernet interface. If
problem persists, contact Technical Support.
Mailbox queue full – COMMREQ
aborted
Check to make sure that the logic application is not sending COMMREQs
faster than the Ethernet Interface can process them. Reduce the rate at
which the application is sending COMMREQs to the Ethernet interface. If
problem persists, contact Technical Support.
Bad local application request;
discarded request
Check for valid COMMREQ command code. If problem persists, contact
Technical Support.
Bad remote application request;
discarded request
Try to validate the operation of the remote node. If problem persists,
contact Technical Support.
Can’t locate remote node;
discarded request
Error reported when message received where IP/MAC address cannot be
resolved. Error may indicate that remote host is not operational on the
network. Check that remote host is operational on network and its
addresses are correct.
Содержание PACSystems RX7i
Страница 45: ......
Страница 54: ...Chapter 4 Configuration GFK 2224Q January 2017 41 Figure 18 CPE400 Advanced Ethernet Configuration LAN1 LAN 2 ...
Страница 80: ...Chapter 4 Configuration GFK 2224Q January 2017 67 ...
Страница 81: ......
Страница 122: ...Chapter 6 Programming EGD Commands GFK 2224Q January 2017 109 ...
Страница 142: ...Chapter 7 Programming SRTP Channel Commands GFK 2224Q January 2017 129 Figure 51 Sample Ladder Logic for COMMREQ ...
Страница 147: ......
Страница 193: ...Chapter 10 OPC UA Server 180 PACSystems RX7i RX3i TCP IP Ethernet Communications User Manual GFK 2224Q Example ...
Страница 202: ...Chapter 10 OPC UA Server GFK 2224Q January 2017 189 Figure 73 Machine Edition Online Command to Set Passwords ...
Страница 211: ......
Страница 253: ...Chapter 12 Diagnostics 240 PACSystems RX7i RX3i TCP IP Ethernet Communications User Manual GFK 2224Q ...
Страница 262: ...Chapter 13 Network Administration GFK 2224Q January 2017 249 ...
Страница 263: ......