Chapter 5. Ethernet Global Data
78
PACSystems* RX7i & RX3i TCP/IP Ethernet Communications User Manual
GFK-2224Q
Obtaining Timestamps from the Ethernet Interface Clock
In this operating mode, the PLC CPU obtains
the timestamp data from the time clock in
the Ethernet interface. The CPU only uses
this timestamp for Ethernet Global Data
exchanges. The timestamp from the
Ethernet interface does not affect the time
of the CPU's internal time clock.
If time synchronization between the CPU
and ETM is lost, as when the CHTIME Station
Manager command is used to change the
ETM time, the CPU uses its own clock for the
time stamp.
CPU
Ethernet
interface
CPU
time
clock
timestamp
time
clock
EGD with
timestamp
Figure 40: Obtaining Timestamps from the Ethernet Interface
Clock
The time clock in the Ethernet Interface is synchronized to either the clock in the CPU or an external SNTP server
on the network. Selection of the timestamp source for Ethernet Global Data is part of the basic configuration of
the Ethernet Interface, as explained in Chapter 4.
PLC's Time Clock
: If this source is selected, the Ethernet
Interface’s built-in time clock is synchronized at power-
up or at restart to the clock in the PLC CPU. The
timestamp information produced by the PLC has a
resolution of 100 microseconds. Because the time
clocks in the PLCs on the network are not synchronized,
EGD timestamps produced by different PLCs cannot be
compared accurately.
CPU
Ethernet
interface
time
clock
timestamp
CPU Time
CPU
time
clock
Figure 41: Obtaining Timestamps from the PLC
Time Clock
SNTP Server's Time Clock:
If this source is selected, the Ethernet Interface’s built-in clock is periodically
synchronized to the clock on an SNTP server on the network. All Ethernet Interfaces configured to use SNTP will
have updated, synchronized timestamps. Therefore, accurate timing comparisons between exchanged data
can be made. If SNTP is used to perform network time synchronization, the timestamp information typically has
±10 millisecond accuracy between PLCs on the same network.
Содержание PACSystems RX7i
Страница 45: ......
Страница 54: ...Chapter 4 Configuration GFK 2224Q January 2017 41 Figure 18 CPE400 Advanced Ethernet Configuration LAN1 LAN 2 ...
Страница 80: ...Chapter 4 Configuration GFK 2224Q January 2017 67 ...
Страница 81: ......
Страница 122: ...Chapter 6 Programming EGD Commands GFK 2224Q January 2017 109 ...
Страница 142: ...Chapter 7 Programming SRTP Channel Commands GFK 2224Q January 2017 129 Figure 51 Sample Ladder Logic for COMMREQ ...
Страница 147: ......
Страница 193: ...Chapter 10 OPC UA Server 180 PACSystems RX7i RX3i TCP IP Ethernet Communications User Manual GFK 2224Q Example ...
Страница 202: ...Chapter 10 OPC UA Server GFK 2224Q January 2017 189 Figure 73 Machine Edition Online Command to Set Passwords ...
Страница 211: ......
Страница 253: ...Chapter 12 Diagnostics 240 PACSystems RX7i RX3i TCP IP Ethernet Communications User Manual GFK 2224Q ...
Страница 262: ...Chapter 13 Network Administration GFK 2224Q January 2017 249 ...
Страница 263: ......