Chapter 5. Ethernet Global Data
88
PACSystems* RX7i & RX3i TCP/IP Ethernet Communications User Manual
GFK-2224Q
The Ethernet Interface will continue supplying time values to the PLC CPU for time-stamping, while it "listens"
for SNTP timing messages from the network. If SNTP messages are received later, the Ethernet Interface will
then synchronize to them.
5.6
Effect of PLC Modes and Actions on EGD Operations
The configuration and operation of Ethernet Global Data may be affected by the PLC’s current mode and by
certain PLC actions:
▪
The normal PLC mode for EGD operation is RUN with Outputs enabled. In this PLC mode, Ethernet Global
Data remains configured and exchanges are both produced and consumed.
▪
If the PLC mode is set to STOP with I/O disabled, the Producer ID remains configured, but production and
consumption stop. Note that while consumed data is not transferred to the PLC memory in this mode, data
from the network is still transferred to the shared memory so that the latest data is available immediately
when the PLC transitions out of STOP with I/O disabled mode.
▪
If configuration is lost, the Ethernet Global Data configuration must be stored again.
PLC Mode or Action
Producer ID
remains
configured
Configuration-Based Exchanges
continue to be
Configured
Produced
Consumed
PLC Mode
RUN-Outputs Enabled
YES
YES
YES
YES
RUN-Outputs Disabled
YES
YES
NO
YES
RUN-SUSPEND I/O
YES
YES
YES
YES
STOP-I/O Enabled
YES
YES
YES
YES
STOP-I/O Disabled
YES
YES
NO
NO
PLC Action
RUN-Store Logic
YES
YES
YES
YES
STOP-Store Logic
YES
YES
STOP-Clear Logic
YES
YES
STOP-Config Store
Replaced
Replaced
STOP-Clear Config
NO
NO
NO
NO
PLC Power Cycle
YES
YES
Ethernet Interface Restart
YES
YES
8
RUN-SUSPEND I/O refers to the SUSIO logic function. (The DOIO logic function does not affect EGD production
or consumption.)
9
Production and consumption is controlled by the PLC Mode as described above.
10
Producer ID and exchange definitions are replaced.
11
Producer ID and exchange states depend on the PLC mode and configuration prior to the action.
Содержание PACSystems RX7i
Страница 45: ......
Страница 54: ...Chapter 4 Configuration GFK 2224Q January 2017 41 Figure 18 CPE400 Advanced Ethernet Configuration LAN1 LAN 2 ...
Страница 80: ...Chapter 4 Configuration GFK 2224Q January 2017 67 ...
Страница 81: ......
Страница 122: ...Chapter 6 Programming EGD Commands GFK 2224Q January 2017 109 ...
Страница 142: ...Chapter 7 Programming SRTP Channel Commands GFK 2224Q January 2017 129 Figure 51 Sample Ladder Logic for COMMREQ ...
Страница 147: ......
Страница 193: ...Chapter 10 OPC UA Server 180 PACSystems RX7i RX3i TCP IP Ethernet Communications User Manual GFK 2224Q Example ...
Страница 202: ...Chapter 10 OPC UA Server GFK 2224Q January 2017 189 Figure 73 Machine Edition Online Command to Set Passwords ...
Страница 211: ......
Страница 253: ...Chapter 12 Diagnostics 240 PACSystems RX7i RX3i TCP IP Ethernet Communications User Manual GFK 2224Q ...
Страница 262: ...Chapter 13 Network Administration GFK 2224Q January 2017 249 ...
Страница 263: ......