Chapter 12. Diagnostics
226
PACSystems* RX7i & RX3i TCP/IP Ethernet Communications User Manual
GFK-2224Q
Error Status (Hex) SRTP Error Code Description
4E11H
Timed out waiting to transfer a mailbox message to the PLC.
4F11H
Timed out waiting for PLC CPU response.
Minor Error Codes for Major Error Code 90H (at Client PLC)
Error Status (Hex) Error Description
0190H
Timeout expired before transfer completed; still waiting on transfer.
0290H
Period expired before transfer completed; still waiting on transfer.
8190H
COMMREQ data block too short for the command.
8290H
COMMREQ data block too short for server PLC node address.
8390H
Invalid server memory type.
8490H
Invalid Program Name.
8590H
Invalid Program Block Name.
8690H
Zero server unit length is not allowed.
8790H
Server unit length is too large.
8890H
Invalid channel number.
8990H
Invalid time unit for period. (Maximum permitted 3965 hours)
8A90H
Period value is too large.
8B90H
Zero server memory starting address is not allowed.
8C90H
Invalid client memory type.
8D90H
Invalid server host address type.
8E90H
Invalid IP address integer value. (Must be 0–255)
8F90H
Invalid IP address class. (Must be valid Class A, B, or C IP address)
May also occur if the destination IP address in the COMMREQ is same as the sender’s IP
address.
9090H
Insufficient TCP connection resources to do request.
9190H
Zero local starting address is not allowed.
9290H
Address length value invalid. Must be 4 for address type 1.
9390H
COMMREQ data block too short for Program Block name (including 0 pad).
9490H
COMMREQ data block too short for Program name (including 0 pad).
9590H
Internal API error. See Controller Fault Table or exception log for details. This problem may
occur due to the Ethernet Interface being asked to perform beyond its capacity. Try
transferring less data per message or establishing fewer simultaneous connections.
9690H
Underlying TCP connection aborted (reset) by server end point.
9790H
Underlying TCP connection aborted by client end point.
9890H
The remote server has no Service Request Processor.
9A90H
Response to session request did not arrive in proper order.
9B90H
Session denied by server PLC.
9C90H
Data response did not arrive in proper order.
9D90H
Data response had unexpected size.
9E90H
Unrecognized COMMREQ command code.
A190H
Invalid CRS word memory type.
A290H
Failed an attempt to update the CRS word.
A390H
Reserved.
A490H
Reserved.
A590H
Reserved.
Содержание PACSystems RX7i
Страница 45: ......
Страница 54: ...Chapter 4 Configuration GFK 2224Q January 2017 41 Figure 18 CPE400 Advanced Ethernet Configuration LAN1 LAN 2 ...
Страница 80: ...Chapter 4 Configuration GFK 2224Q January 2017 67 ...
Страница 81: ......
Страница 122: ...Chapter 6 Programming EGD Commands GFK 2224Q January 2017 109 ...
Страница 142: ...Chapter 7 Programming SRTP Channel Commands GFK 2224Q January 2017 129 Figure 51 Sample Ladder Logic for COMMREQ ...
Страница 147: ......
Страница 193: ...Chapter 10 OPC UA Server 180 PACSystems RX7i RX3i TCP IP Ethernet Communications User Manual GFK 2224Q Example ...
Страница 202: ...Chapter 10 OPC UA Server GFK 2224Q January 2017 189 Figure 73 Machine Edition Online Command to Set Passwords ...
Страница 211: ......
Страница 253: ...Chapter 12 Diagnostics 240 PACSystems RX7i RX3i TCP IP Ethernet Communications User Manual GFK 2224Q ...
Страница 262: ...Chapter 13 Network Administration GFK 2224Q January 2017 249 ...
Страница 263: ......