Chapter 9. Modbus/TCP Client
152
PACSystems* RX7i & RX3i TCP/IP Ethernet Communications User Manual
GFK-2224Q
Command 3003, Example 3 – Read Exception Status
Read the Exception Status from the remote Modbus/TCP server. Store the Exception Data at location %Q4 (bit
mode). Return the COMMREQ Status word to %R10.
Dec (Hex)
Word 1
00008 (0008) Length of Channel command Data Block
Word 2
00000 (0000) Always 0 (no-wait mode request)
Word 3
00008 (0008) Memory type of CRS word (%R)
Word 4
00009 (0009) CRS word address minus 1 (%R10)
Word 5
00000 (0000) Reserved
Word 6
00000 (0000) Reserved
Word 7
03003 (0BBB) Read from a Modbus/TCP Device
Word 8
00006 (0006) Channel number (6)
Word 9
00007 (0007) Modbus Function Code (Read Exception Status)
Word 10
00072 (0048) Local PLC Memory Type
Word 11
00004 (0004) Local PLC Starting Address
Word 12
00000 (0000) Reserved
Word 13
00001 (0001) Data Size
Word 14
00001 (0001) Unit Identifier
(Word 7) Channel Command Number:
Word 7 identifies the COMMREQ as a Read Exception Status from the
Modbus/TCP device.
(Word 8) Channel Number:
Word 8 identifies the channel number previously allocated for communication with
the remote Modbus/TCP server.
(Word 9) Modbus Function Code:
Word 9 specifies Modbus Function Code 7, Read Exception Status.
(Word 10) Local PLC Memory Type:
Words 10-11 specify the location in the local PLC where the Ethernet
interface will store data received from the remote device. Valid values for Word 10 are listed on page
(Word 11) Local PLC Memory Address:
Word 11 determines the starting address in the local PLC in which
the data from the remote device is to be stored. The value entered is the offset (1-based) from the beginning of
PLC memory for the memory type and mode specified in Word 10. This offset will be either in bits, bytes, or
words depending on the mode specified. Valid ranges of values depend on the PLC’s memory ranges. Be sure
this area is large enough to contain the requested data without overwriting other application data.
(Word 12) Reserved:
Word 12 is reserved and must be set to zero.
(Word 13) Data Size:
Word 13 is the data size and must be set to 1.
(Word 14) Unit Identifier:
This field is typically used by Ethernet to Serial bridges to specify the address of a
Modbus Slave on a multi-drop link. The Modbus/TCP Unit Identifier is a special control code used in a
Modbus/TCP message block.
Содержание PACSystems RX7i
Страница 45: ......
Страница 54: ...Chapter 4 Configuration GFK 2224Q January 2017 41 Figure 18 CPE400 Advanced Ethernet Configuration LAN1 LAN 2 ...
Страница 80: ...Chapter 4 Configuration GFK 2224Q January 2017 67 ...
Страница 81: ......
Страница 122: ...Chapter 6 Programming EGD Commands GFK 2224Q January 2017 109 ...
Страница 142: ...Chapter 7 Programming SRTP Channel Commands GFK 2224Q January 2017 129 Figure 51 Sample Ladder Logic for COMMREQ ...
Страница 147: ......
Страница 193: ...Chapter 10 OPC UA Server 180 PACSystems RX7i RX3i TCP IP Ethernet Communications User Manual GFK 2224Q Example ...
Страница 202: ...Chapter 10 OPC UA Server GFK 2224Q January 2017 189 Figure 73 Machine Edition Online Command to Set Passwords ...
Страница 211: ......
Страница 253: ...Chapter 12 Diagnostics 240 PACSystems RX7i RX3i TCP IP Ethernet Communications User Manual GFK 2224Q ...
Страница 262: ...Chapter 13 Network Administration GFK 2224Q January 2017 249 ...
Страница 263: ......