Chapter 5. Ethernet Global Data
90
PACSystems* RX7i & RX3i TCP/IP Ethernet Communications User Manual
GFK-2224Q
Effects of Modifying Consumed Exchange Parameters
For consumed exchanges, the combination of Producer ID and Exchange ID uniquely identifies the exchange.
Modifying any of these parameters will make the exchange incompatible and require an update to the
producer to restore compatibility.
Parameter
Behavior
Producer ID
Redefines the exchange. Causes a major signature change in the producer. Exchange
will be incompatible.
Group ID
Determines the producer of the exchange and may affect compatibility. For details,
refer to “Sending an Ethernet Global Data Exchange to Multiple Consumers” on page
Exchange ID
Redefines the exchange. Causes a major signature change in the producer. Exchange
will be incompatible.
Adapter Name
Deletes an exchange from one Ethernet module and adds an exchange to another.
Assuming no other parameters change, this will not affect compatibility
To any EGD Class 2 device sending commands that operate on this exchange, it will
appear that the exchange has been deleted. The Class 2 device must be updated to
direct the commands to the IP address of the adapter where the exchange has been
moved.
Update Timeout
Modifies existing exchange. Does not affect compatibility. Note that decreasing a
consumed exchange’s update timeout without updating the corresponding
producer’s production period may cause timeouts.
Effects of Modifying Produced Exchange Parameters
Parameter
Behavior
Exchange ID
Redefines the exchange. Causes a major signature change in the producer.
Adapter Name
Deletes an exchange from one Ethernet module and adds an exchange to another.
Assuming no other parameters change, modifying this parameter does not affect
compatibility.
Destination Type
Determines the consumer(s) of the exchange and may affect compatibility. For
details, refer to “Sending an Ethernet Global Data Exchange to Multiple Consumers”
on page 73.
Destination
Determines the consumer(s) of the exchange. Affects compatibility.
Produced Period
Modifies the existing exchange. Does not affect compatibility.
Produce In Backup
Mode
If the unit is in backup mode, modifying this parameter will cause the production of
the exchange to start if being set to TRUE and stop if being set to FALSE.
If the primary unit is the active unit, modifying this parameter will have no immediate
effect.
If the secondary unit is the active unit, modifying this parameter will cause an
incompatibility because it changes the exchange ID.
Note:
If this option is set to FALSE for all exchanges in a system, this setting cannot
be modified in a run mode store. If at least one exchange has this setting as
TRUE in the prior stop mode store, then this setting can be modified for other
exchanges in a run mode store.
Содержание PACSystems RX7i
Страница 45: ......
Страница 54: ...Chapter 4 Configuration GFK 2224Q January 2017 41 Figure 18 CPE400 Advanced Ethernet Configuration LAN1 LAN 2 ...
Страница 80: ...Chapter 4 Configuration GFK 2224Q January 2017 67 ...
Страница 81: ......
Страница 122: ...Chapter 6 Programming EGD Commands GFK 2224Q January 2017 109 ...
Страница 142: ...Chapter 7 Programming SRTP Channel Commands GFK 2224Q January 2017 129 Figure 51 Sample Ladder Logic for COMMREQ ...
Страница 147: ......
Страница 193: ...Chapter 10 OPC UA Server 180 PACSystems RX7i RX3i TCP IP Ethernet Communications User Manual GFK 2224Q Example ...
Страница 202: ...Chapter 10 OPC UA Server GFK 2224Q January 2017 189 Figure 73 Machine Edition Online Command to Set Passwords ...
Страница 211: ......
Страница 253: ...Chapter 12 Diagnostics 240 PACSystems RX7i RX3i TCP IP Ethernet Communications User Manual GFK 2224Q ...
Страница 262: ...Chapter 13 Network Administration GFK 2224Q January 2017 249 ...
Страница 263: ......