Chapter 12. Diagnostics
208
PACSystems* RX7i & RX3i TCP/IP Ethernet Communications User Manual
GFK-2224Q
12.2
Diagnostic Tools Available for Troubleshooting
There are several tools to assist you in diagnosing problems with the Ethernet Interface and the network.
▪
Use the
Ethernet Interface LEDs
to troubleshoot a problem on power-up of the Ethernet Interface and
for an immediate visual summary of the operational state of the Interface.
▪
Use the Controller Fault Table to troubleshoot a problem once the Interface is running. It provides a
record of exceptions logged by the PLC, the Ethernet Interface, and other I/O and communications
modules. The Controller Fault Table is accessed through the programming software or, if supported, in
a web browser.
▪
For Controller Fault Table entries generated by the Ethernet Interface, the Detailed Fault Data for that
entry contains the same data as the corresponding event in the Ethernet Interface’s exception log.
Refer to GFK-2225,
TCP/IP Ethernet Communications for the PACSystems Station Manager Manual,
for
information on how to interpret Ethernet exception log events.
▪
Use the Ethernet Status Data to troubleshoot the Ethernet Interface status
▪
For Ethernet Global Data operation, the EGD Management Tool can be used to check online operation
of the EGD network and Exchange Status words can be used to troubleshoot exchange operations.
▪
Use the Station Manager to troubleshoot a problem with the Ethernet Interface, the network, PLC
backplane communication, or with your application. The LOG, TALLY, EXS, CHANNEL, STAT, and
XCHANGE Station Manager commands are especially useful.
-
The LOG command provides a complete record of exceptions occurring with the network and
Interface.
-
The TALLY command provides statistics about operation and performance of the network and
Interface.
-
The EXS command provides information about COMMREQs.
-
The CHANNEL command displays detailed information about a specified SRTP or Modbus/TCP
communication channel.
-
The STAT command provides the current status of specific components of the Ethernet interface.
Of particular use, the STAT V and STAT H commands provide SRTP server and SRTP channel status,
respectively. The STAT O and STAT M commands provide Modbus/TCP server and channel status,
respectively. The STAT G command provides the current status on the operation of EGD
communications on the Interface.
-
The XCHANGE command displays detailed information about a specified Ethernet Global Data
exchange.
Refer to GFK-2225,
TCP/IP Ethernet Communications for PACSystems Station Manager Manual
, for information
on how to access and use the Station Manager software.
Содержание PACSystems RX7i
Страница 45: ......
Страница 54: ...Chapter 4 Configuration GFK 2224Q January 2017 41 Figure 18 CPE400 Advanced Ethernet Configuration LAN1 LAN 2 ...
Страница 80: ...Chapter 4 Configuration GFK 2224Q January 2017 67 ...
Страница 81: ......
Страница 122: ...Chapter 6 Programming EGD Commands GFK 2224Q January 2017 109 ...
Страница 142: ...Chapter 7 Programming SRTP Channel Commands GFK 2224Q January 2017 129 Figure 51 Sample Ladder Logic for COMMREQ ...
Страница 147: ......
Страница 193: ...Chapter 10 OPC UA Server 180 PACSystems RX7i RX3i TCP IP Ethernet Communications User Manual GFK 2224Q Example ...
Страница 202: ...Chapter 10 OPC UA Server GFK 2224Q January 2017 189 Figure 73 Machine Edition Online Command to Set Passwords ...
Страница 211: ......
Страница 253: ...Chapter 12 Diagnostics 240 PACSystems RX7i RX3i TCP IP Ethernet Communications User Manual GFK 2224Q ...
Страница 262: ...Chapter 13 Network Administration GFK 2224Q January 2017 249 ...
Страница 263: ......