GE Multilin
G60 Generator Protection System
B-47
APPENDIX B
B.4 MEMORY MAPPING
B
AFE2
...Repeated for IEC 61850 GGIO4 analog input 31
AFE9
...Repeated for IEC 61850 GGIO4 analog input 32
IEC 61850 Logical Node Name Prefixes (Read/Write Setting)
AB30
IEC 61850 Logical Node LPHD1 Name Prefix
0 to 65534
---
1
F206
(None)
AB33
IEC 61850 Logical Node PIOCx Name Prefix (72 items)
0 to 65534
---
1
F206
(None)
AC0B
IEC 61850 Logical Node PTOCx Name Prefix (24 items)
0 to 65534
---
1
F206
(None)
AC53
IEC 61850 Logical Node PTUVx Name Prefix (12 items)
0 to 65534
---
1
F206
(None)
AC77
IEC 61850 Logical Node PTOVx Name Prefix (8 items)
0 to 65534
---
1
F206
(None)
AC8F
IEC 61850 Logical Node PDISx Name Prefix (10 items)
0 to 65534
---
1
F206
(None)
ACAD
IEC 61850 Logical Node RRBFx Name Prefix (24 items)
0 to 65534
---
1
F206
(None)
ACF5
IEC 61850 Logical Node RPSBx Name Prefix
0 to 65534
---
1
F206
(None)
ACF8
IEC 61850 Logical Node RRECx Name Prefix (6 items)
0 to 65534
---
1
F206
(None)
AD0A
IEC 61850 Logical Node MMXUx Name Prefix (6 items)
0 to 65534
---
1
F206
(None)
AD1C
IEC 61850 Logical Node GGIOx Name Prefix (4 items)
0 to 65534
---
1
F206
(None)
AD28
IEC 61850 Logical Node RFLOx Name Prefix (5 items)
0 to 65534
---
1
F206
(None)
AD37
IEC 61850 Logical Node XCBRx Name Prefix (2 items)
0 to 65534
---
1
F206
(None)
AD3D
IEC 61850 Logical Node PTRCx Name Prefix (2 items)
0 to 65534
---
1
F206
(None)
AD43
IEC 61850 Logical Node PDIFx Name Prefix (4 items)
0 to 65534
---
1
F206
(None)
AD4F
IEC 61850 Logical Node MMXNx Name Prefix (37 items)
0 to 65534
---
1
F206
(None)
IEC 61850 GOOSE/GSSE Configuration (Read/Write Setting)
B01C
Default GOOSE/GSSE Update Time
1 to 60
s
1
F001
60
B01D
IEC 61850 GSSE Function (GsEna)
0 to 1
---
1
F102
1 (Enabled)
B013
IEC 61850 GSSE ID
---
---
---
F209
“GSSEOut”
B03F
IEC 61850 GOOSE Function (GoEna)
0 to 1
---
1
F102
0 (Disabled)
B040
IEC 61850 GSSE Destination MAC Address
---
---
---
F072
0
B043
IEC 61850 Standard GOOSE ID
---
---
---
F209
“GOOSEOut”
B064
IEC 61850 Standard GOOSE Destination MAC Address
---
---
---
F072
0
B067
IEC 61850 GOOSE VLAN Transmit Priority
0 to 7
---
1
F001
4
B068
IEC 61850 GOOSE VLAN ID
0 to 4095
---
1
F001
0
B069
IEC 61850 GOOSE ETYPE APPID
0 to 16383
---
1
F001
0
B06A
Reserved (2 items)
0 to 1
---
1
F001
0
IEC 61850 Server Configuration (Read/Write Settings/Commands)
B06C
TCP Port Number for the IEC 61850 / MMS Protocol
1 to 65535
---
1
F001
102
B06D
IEC 61850 Logical Device Name
---
---
---
F213
“IECName”
B07D
IEC 61850 Logical Device Instance
---
---
---
F213
“LDInst”
B08D
IEC 61850 LPHD Location
---
---
---
F204
“Location”
B0B5
Include non-IEC 61850 Data
0 to 1
---
1
F102
0 (Disabled)
B06B
IEC 61850 Server Data Scanning Function
0 to 1
---
1
F102
0 (Disabled)
B0B7
Reserved (15 items)
IEC 61850 MMXU Deadbands (Read/Write Setting) (6 modules)
B0C0
IEC 61850 MMXU TotW Deadband 1
0.001 to 100
%
0.001
F003
10000
B0C2
IEC 61850 MMXU TotVAr Deadband 1
0.001 to 100
%
0.001
F003
10000
B0C4
IEC 61850 MMXU TotVA Deadband 1
0.001 to 100
%
0.001
F003
10000
B0C6
IEC 61850 MMXU TotPF Deadband 1
0.001 to 100
%
0.001
F003
10000
B0C8
IEC 61850 MMXU Hz Deadband 1
0.001 to 100
%
0.001
F003
10000
B0CA
IEC 61850 MMXU PPV.phsAB Deadband 1
0.001 to 100
%
0.001
F003
10000
B0CC
IEC 61850 MMXU PPV.phsBC Deadband 1
0.001 to 100
%
0.001
F003
10000
B0CE
IEC 61850 MMXU PPV.phsCA Deadband 1
0.001 to 100
%
0.001
F003
10000
B0D0
IEC 61850 MMXU PhV.phsADeadband 1
0.001 to 100
%
0.001
F003
10000
B0D2
IEC 61850 MMXU PhV.phsB Deadband 1
0.001 to 100
%
0.001
F003
10000
B0D4
IEC 61850 MMXU PhV.phsC Deadband 1
0.001 to 100
%
0.001
F003
10000
B0D6
IEC 61850 MMXU A.phsA Deadband 1
0.001 to 100
%
0.001
F003
10000
B0D8
IEC 61850 MMXU A.phsB Deadband 1
0.001 to 100
%
0.001
F003
10000
B0DA
IEC 61850 MMXU A.phsC Deadband 1
0.001 to 100
%
0.001
F003
10000
Table B–9: MODBUS MEMORY MAP (Sheet 40 of 58)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание G60 UR Series
Страница 2: ......
Страница 4: ......
Страница 12: ...xii G60 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Страница 32: ...1 20 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 102: ...3 48 G60 Generator Protection System GE Multilin 3 4 MANAGED ETHERNET SWITCH MODULES 3 HARDWARE 3 ...
Страница 132: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 392: ...5 260 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 418: ...6 26 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 446: ...8 18 G60 Generator Protection System GE Multilin 8 3 ENERVISTA SECURITY MANAGEMENT SYSTEM 8 SECURITY 8 ...
Страница 452: ...9 6 G60 Generator Protection System GE Multilin 9 1 PHASE DISTANCE THROUGH POWER TRANSFORMERS 9 THEORY OF OPERATION 9 ...
Страница 482: ...A 12 G60 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIXA A ...
Страница 604: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Страница 616: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Страница 634: ...x G60 Generator Protection System GE Multilin INDEX ...