5-76
G60 Generator Protection System
GE Multilin
5.4 SYSTEM SETUP
5 SETTINGS
5
•
SWITCH 1 OPEN:
This setting selects an operand that creates a programmable signal to operate an output relay to
open disconnect switch 1.
•
SWITCH 1 BLK OPEN
: This setting selects an operand that prevents opening of the disconnect switch. This setting
can be used for select-before-operate functionality or to block operation from a panel switch or from SCADA.
•
SWITCH 1 CLOSE:
This setting selects an operand that creates a programmable signal to operate an output relay to
close disconnect switch 1.
•
SWITCH 1 BLK CLOSE
: This setting selects an operand that prevents closing of the disconnect switch. This setting
can be used for select-before-operate functionality or to block operation from a panel switch or from SCADA.
•
SWTCH 1
Φ
A/3P CLSD:
This setting selects an operand, usually a contact input connected to a disconnect switch
auxiliary position tracking mechanism. This input should be a normally-open 52/a status input to create a logic 1 when
the disconnect switch is closed. If the
SWITCH 1 MODE
setting is selected as “3-Pole”, this setting selects a single input
as the operand used to track the disconnect switch open or closed position. If the mode is selected as “1-Pole”, the
input mentioned above is used to track phase A and the
SWITCH 1
Φ
B
and
SWITCH 1
Φ
C
settings select operands to
track phases B and C, respectively.
•
SWITCH 1
Φ
A/3P OPND:
This setting selects an operand, usually a contact input, that should be a normally-closed
52/b status input to create a logic 1 when the disconnect switch is open. If a separate 52/b contact input is not avail-
able, then the inverted
SWITCH 1 CLOSED
status signal can be used.
•
SWITCH 1
Φ
B CLOSED:
If the mode is selected as three-pole, this setting has no function. If the mode is selected as
single-pole, this input is used to track the disconnect switch phase B closed position as above for phase A.
•
SWITCH 1
Φ
B OPENED:
If the mode is selected as three-pole, this setting has no function. If the mode is selected as
single-pole, this input is used to track the disconnect switch phase B opened position as above for phase A.
•
SWITCH 1
Φ
C CLOSED:
If the mode is selected as three-pole, this setting has no function. If the mode is selected as
single-pole, this input is used to track the disconnect switch phase C closed position as above for phase A.
•
SWITCH 1
Φ
C OPENED:
If the mode is selected as three-pole, this setting has no function. If the mode is selected as
single-pole, this input is used to track the disconnect switch phase C opened position as above for phase A.
•
SWITCH 1 Toperate
: This setting specifies the required interval to overcome transient disagreement between the 52/a
and 52/b auxiliary contacts during disconnect switch operation. If transient disagreement still exists after this time has
expired, the
SWITCH 1 BAD STATUS
FlexLogic™ operand is asserted from alarm or blocking purposes.
•
SWITCH 1 ALARM DELAY:
This setting specifies the delay interval during which a disagreement of status among the
three-pole position tracking operands will not declare a pole disagreement. This allows for non-simultaneous operation
of the poles.
IEC 61850 functionality is permitted when the G60 is in “Programmed” mode and not in the local control mode.
NOTE
Содержание G60 UR Series
Страница 2: ......
Страница 4: ......
Страница 12: ...xii G60 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Страница 32: ...1 20 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 102: ...3 48 G60 Generator Protection System GE Multilin 3 4 MANAGED ETHERNET SWITCH MODULES 3 HARDWARE 3 ...
Страница 132: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 392: ...5 260 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 418: ...6 26 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 446: ...8 18 G60 Generator Protection System GE Multilin 8 3 ENERVISTA SECURITY MANAGEMENT SYSTEM 8 SECURITY 8 ...
Страница 452: ...9 6 G60 Generator Protection System GE Multilin 9 1 PHASE DISTANCE THROUGH POWER TRANSFORMERS 9 THEORY OF OPERATION 9 ...
Страница 482: ...A 12 G60 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIXA A ...
Страница 604: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Страница 616: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Страница 634: ...x G60 Generator Protection System GE Multilin INDEX ...