5-168
G60 Generator Protection System
GE Multilin
5.6 GROUPED ELEMENTS
5 SETTINGS
5
The following examples explain how the restraining signal is created for maximum sensitivity and security. These examples
clarify the operating principle and provide guidance for testing of the element.
EXAMPLE 1: EXTERNAL SINGLE-LINE-TO-GROUND FAULT
Given the following inputs: IA = 1 pu
∠
0°, IB = 0, IC = 0, and IG = 1 pu
∠
180°
The relay calculates the following values:
Igd = 0,
,
,
, and Igr = 2 pu
The restraining signal is twice the fault current. This gives extra margin should the phase or neutral CT saturate.
EXAMPLE 2: EXTERNAL HIGH-CURRENT SLG FAULT
Given the following inputs: IA = 10 pu
∠
0°, IB = 0, IC = 0, and IG = 10 pu
∠
–180°
The relay calculates the following values:
Igd = 0,
,
,
, and Igr = 20 pu.
EXAMPLE 3: EXTERNAL HIGH-CURRENT THREE-PHASE SYMMETRICAL FAULT
Given the following inputs: IA = 10 pu
∠
0°, IB = 10 pu
∠
–120°, IC = 10 pu
∠
120°, and IG = 0 pu
The relay calculates the following values:
Igd = 0,
,
,
, and Igr = 10 pu.
EXAMPLE 4: INTERNAL LOW-CURRENT SINGLE-LINE-TO-GROUND FAULT UNDER FULL LOAD
Given the following inputs: IA = 1.10 pu
∠
0°, IB = 1.0 pu
∠
–120°, IC = 1.0 pu
∠
120°, and IG = 0.05 pu
∠
0°
The relay calculates the following values:
I_0 = 0.033 pu
∠
0°, I_2 = 0.033 pu
∠
0°, and I_1 = 1.033 pu
∠
0°
Igd = abs(3
×
0.0333 + 0.05) = 0.15 pu, IR0 = abs(3
×
0.033 – (0.05)) = 0.05 pu, IR2 = 3
×
0.033 = 0.10 pu,
IR1 = 1.033 / 8 = 0.1292 pu, and Igr = 0.1292 pu
Despite very low fault current level the differential current is above 100% of the restraining current.
EXAMPLE 5: INTERNAL LOW-CURRENT, HIGH-LOAD SINGLE-LINE-TO-GROUND FAULT WITH NO FEED FROM
THE GROUND
Given the following inputs: IA = 1.10 pu
∠
0°, IB = 1.0 pu
∠
–120°, IC = 1.0 pu
∠
120°, and IG = 0.0 pu
∠
0°
The relay calculates the following values:
I_0 = 0.033 pu
∠
0°, I_2 = 0.033 pu
∠
0°, and I_1 = 1.033 pu
∠
0°
Igd = abs(3
×
0.0333 + 0.0) = 0.10 pu, IR0 = abs(3
×
0.033 – (0.0)) = 0.10 pu, IR2 = 3
×
0.033 = 0.10 pu,
IR1 = 1.033 / 8 = 0.1292 pu, and Igr = 0.1292 pu
Despite very low fault current level the differential current is above 75% of the restraining current.
EXAMPLE 6: INTERNAL HIGH-CURRENT SINGLE-LINE-TO-GROUND FAULT WITH NO FEED FROM THE GROUND
Given the following inputs: IA = 10 pu
∠
0°, IB = 0 pu, IC = 0 pu, and IG = 0 pu
The relay calculates the following values:
I_0 = 3.3 pu
∠
0°, I_2 = 3.3 pu
∠
0°, and I_1 = 3.3 pu
∠
0°
Igd = abs(3
×
3.3 + 0.0) = 10 pu, IR0 = abs(3
×
3.3 – (0.0)) = 10 pu, IR2 = 3
×
3.3 = 10 pu, IR1 = 3
×
(3.33 – 3.33) = 0
pu, and Igr = 10 pu
The differential current is 100% of the restraining current.
IR0
abs 3
1
3
---
×
1
–
(
)
–
⎝
⎠
⎛
⎞
2 pu
=
=
IR2
3
1
3
---
×
1 pu
=
=
IR1
1 3
⁄
8
----------
0.042 pu
=
=
IR0
abs 3
1
3
---
×
10
–
(
)
–
⎝
⎠
⎛
⎞
20 pu
=
=
IR2
3
10
3
------
×
10 pu
=
=
IR1
3
10
3
------
10
3
------
–
⎝
⎠
⎛
⎞
×
0
=
=
IR0
abs 3
0
×
0
( )
–
(
)
0 pu
=
=
IR2
3
0
×
0 pu
=
=
IR1
3
10
3
------
0
–
⎝
⎠
⎛
⎞
×
10 pu
=
=
Содержание G60 UR Series
Страница 2: ......
Страница 4: ......
Страница 12: ...xii G60 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Страница 32: ...1 20 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 102: ...3 48 G60 Generator Protection System GE Multilin 3 4 MANAGED ETHERNET SWITCH MODULES 3 HARDWARE 3 ...
Страница 132: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 392: ...5 260 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 418: ...6 26 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 446: ...8 18 G60 Generator Protection System GE Multilin 8 3 ENERVISTA SECURITY MANAGEMENT SYSTEM 8 SECURITY 8 ...
Страница 452: ...9 6 G60 Generator Protection System GE Multilin 9 1 PHASE DISTANCE THROUGH POWER TRANSFORMERS 9 THEORY OF OPERATION 9 ...
Страница 482: ...A 12 G60 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIXA A ...
Страница 604: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Страница 616: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Страница 634: ...x G60 Generator Protection System GE Multilin INDEX ...