GE Multilin
G60 Generator Protection System
B-33
APPENDIX B
B.4 MEMORY MAPPING
B
7078
Phase Distance Zone 1 Events
0 to 1
---
1
F102
0 (Disabled)
707A
Phase Distance Zone 1 RCA
30 to 90
degrees
1
F001
85
707B
Phase Distance Zone 1 DIR RCA
30 to 90
degrees
1
F001
85
707C
Phase Distance Zone 1 DIR Comp Limit
30 to 90
degrees
1
F001
90
7081
Phase Distance Zone 1 Volt Limit
0 to 5
pu
0.001
F001
0
7082
Phase Distance Zone 1 Transformer Voltage Connection
0 to 12
---
1
F153
0 (None)
7083
Phase Distance Zone 1 Transformer Current Connection
0 to 12
---
1
F153
0 (None)
7084
Phase Distance Zone 1 Rev Reach
0.02 to 500
ohms
0.01
F001
200
7085
Phase Distance Zone 1 Rev Reach RCA
30 to 90
degrees
1
F001
85
7086
Reserved (10 items)
---
---
---
F001
0
7090
...Repeated for Phase Distance Zone 2
70B0
...Repeated for Phase Distance Zone 3
Phase Directional Overcurrent (Read/Write Grouped Setting) (2 modules)
7260
Phase Directional Overcurrent 1 Function
0 to 1
---
1
F102
0 (Disabled)
7261
Phase Directional Overcurrent 1 Source
0 to 5
---
1
F167
0 (SRC 1)
7262
Phase Directional Overcurrent 1 Block
0 to 65535
---
1
F300
0
7263
Phase Directional Overcurrent 1 ECA
0 to 359
---
1
F001
30
7264
Phase Directional Overcurrent 1 Pol V Threshold
0 to 3
pu
0.001
F001
700
7265
Phase Directional Overcurrent 1 Block Overcurrent
0 to 1
---
1
F126
0 (No)
7266
Phase Directional Overcurrent 1 Target
0 to 2
---
1
F109
0 (Self-reset)
7267
Phase Directional Overcurrent 1 Events
0 to 1
---
1
F102
0 (Disabled)
7268
Reserved (8 items)
0 to 1
---
1
F001
0
7270
...Repeated for Phase Directional Overcurrent 2
Neutral Directional Overcurrent (Read/Write Grouped Setting) (2 modules)
7280
Neutral Directional Overcurrent 1 Function
0 to 1
---
1
F102
0 (Disabled)
7281
Neutral Directional Overcurrent 1 Source
0 to 5
---
1
F167
0 (SRC 1)
7282
Neutral Directional Overcurrent 1 Polarizing
0 to 2
---
1
F230
0 (Voltage)
7283
Neutral Directional Overcurrent 1 Forward ECA
-90 to 90
° Lag
1
F002
75
7284
Neutral Directional Overcurrent 1 Forward Limit Angle
40 to 90
degrees
1
F001
90
7285
Neutral Directional Overcurrent 1 Forward Pickup
0.002 to 30
pu
0.001
F001
50
7286
Neutral Directional Overcurrent 1 Reverse Limit Angle
40 to 90
degrees
1
F001
90
7287
Neutral Directional Overcurrent 1 Reverse Pickup
0.002 to 30
pu
0.001
F001
50
7288
Neutral Directional Overcurrent 1 Target
0 to 2
---
1
F109
0 (Self-reset)
7289
Neutral Directional Overcurrent 1 Block
0 to 65535
---
1
F300
0
728A
Neutral Directional Overcurrent 1 Events
0 to 1
---
1
F102
0 (Disabled)
728B
Neutral Directional Overcurrent 1 Polarizing Voltage
0 to 1
---
1
F231
0 (Calculated V0)
728C
Neutral Directional Overcurrent 1 Op Current
0 to 1
---
1
F196
0 (Calculated 3I0)
728D
Neutral Directional Overcurrent 1 Offset
0 to 250
ohms
0.01
F001
0
728E
Neutral Directional Overcurrent 1 Pos Seq Restraint
0 to 0.5
---
0.001
F001
63
728F
Reserved
0 to 1
---
1
F001
0
7290
...Repeated for Neutral Directional Overcurrent 2
Negative-sequence directional overcurrent (read/write grouped settings) (2 modules)
72A0
Negative Sequence Directional Overcurrent 1 Function
0 to 1
---
1
F102
0 (Disabled)
72A1
Negative Sequence Directional Overcurrent 1 Source
0 to 5
---
1
F167
0 (SRC 1)
72A2
Negative Sequence Directional Overcurrent 1 Type
0 to 1
---
1
F179
0 (Neg Sequence)
72A3
Neg Sequence Directional Overcurrent 1 Forward ECA
0 to 90
° Lag
1
F002
75
72A4
Neg Seq Directional Overcurrent 1 Forward Limit Angle
40 to 90
degrees
1
F001
90
72A5
Neg Sequence Directional Overcurrent 1 Forward Pickup
0.015 to 30
pu
0.05
F001
5
72A6
Neg Seq Directional Overcurrent 1 Reverse Limit Angle
40 to 90
degrees
1
F001
90
72A7
Neg Sequence Directional Overcurrent 1 Reverse Pickup
0.015 to 30
pu
0.05
F001
5
72A8
Negative Sequence Directional Overcurrent 1 Target
0 to 2
---
1
F109
0 (Self-reset)
72A9
Negative Sequence Directional Overcurrent 1 Block
0 to 65535
---
1
F300
0
72AA
Negative Sequence Directional Overcurrent 1 Events
0 to 1
---
1
F102
0 (Disabled)
72AB
Negative Sequence Directional Overcurrent 1 Offset
0 to 250
ohms
0.01
F001
0
Table B–9: MODBUS MEMORY MAP (Sheet 26 of 58)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание G60 UR Series
Страница 2: ......
Страница 4: ......
Страница 12: ...xii G60 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Страница 32: ...1 20 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 102: ...3 48 G60 Generator Protection System GE Multilin 3 4 MANAGED ETHERNET SWITCH MODULES 3 HARDWARE 3 ...
Страница 132: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 392: ...5 260 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 418: ...6 26 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 446: ...8 18 G60 Generator Protection System GE Multilin 8 3 ENERVISTA SECURITY MANAGEMENT SYSTEM 8 SECURITY 8 ...
Страница 452: ...9 6 G60 Generator Protection System GE Multilin 9 1 PHASE DISTANCE THROUGH POWER TRANSFORMERS 9 THEORY OF OPERATION 9 ...
Страница 482: ...A 12 G60 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIXA A ...
Страница 604: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Страница 616: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Страница 634: ...x G60 Generator Protection System GE Multilin INDEX ...