8-15
8 SECURITY
8.3 ENERVISTA SECURITY MANAGEMENT SYSTEM
8
8.3ENERVISTA SECURITY MANAGEMENT SYSTEM
8.3.1 OVERVIEW
The EnerVista security management system is a role-based access control (RBAC) system that allows a security adminis-
trator to easily manage the security privileges of multiple users. This allows for access control of URPlus-series devices by
multiple personnel within a substation and conforms to the principles of RBAC as defined in ANSI INCITS 359-2004. The
EnerVista security management system is disabled by default to allow the administrator direct access to the EnerVista soft-
ware after installation. It is recommended that security be enabled before placing the device in service.
8.3.2 ENABLING THE SECURITY MANAGEMENT SYSTEM
The EnerVista security management system is disabled by default. This allows access to the device immediately after
installation. When security is disabled, all users are granted administrator access.
1.
Select the
Security > User Management
menu item to open the user management configuration window.
2.
Check the
Enable Security
box in the lower-left corner to enable the security management system.
Security is now enabled for the EnerVista UR Setup software. It will now be necessary to enter a username and password
upon starting the software.
8.3.3 ADDING A NEW USER
The following pre-requisites are required to add new users to the EnerVista security management system.
•
The user adding the new user must have administrator rights.
•
The EnerVista security management system must be enabled.
The following procedure describes how to add new users.
1.
Select the
Security > User Management
menu item to open the user management configuration window.
2.
Enter a username in the
User
field. The username must be between 4 and 20 characters in length.
Содержание G60 UR Series
Страница 2: ......
Страница 4: ......
Страница 12: ...xii G60 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Страница 32: ...1 20 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 102: ...3 48 G60 Generator Protection System GE Multilin 3 4 MANAGED ETHERNET SWITCH MODULES 3 HARDWARE 3 ...
Страница 132: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 392: ...5 260 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 418: ...6 26 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 446: ...8 18 G60 Generator Protection System GE Multilin 8 3 ENERVISTA SECURITY MANAGEMENT SYSTEM 8 SECURITY 8 ...
Страница 452: ...9 6 G60 Generator Protection System GE Multilin 9 1 PHASE DISTANCE THROUGH POWER TRANSFORMERS 9 THEORY OF OPERATION 9 ...
Страница 482: ...A 12 G60 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIXA A ...
Страница 604: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Страница 616: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Страница 634: ...x G60 Generator Protection System GE Multilin INDEX ...