GE Multilin
G60 Generator Protection System
3-23
3 HARDWARE
3.2 WIRING
3
3.2.8 RS232 FACEPLATE PORT
A 9-pin RS232C serial port is located on the G60 faceplate for programming with a personal computer. All that is required
to use this interface is a personal computer running the EnerVista UR Setup software provided with the relay. Cabling for
the RS232 port is shown in the following figure for both 9-pin and 25-pin connectors.
The baud rate for this port is fixed at
19200 bps
.
Figure 3–23: RS232 FACEPLATE PORT CONNECTION
3.2.9 CPU COMMUNICATION PORTS
a) OPTIONS
In addition to the faceplate RS232 port, the G60 provides two additional communication ports or a managed six-port Ether-
net switch, depending on the installed CPU module.
The CPU modules do not require a surge ground connection.
Table 3–3: CPU MODULE COMMUNICATIONS
CPU TYPE
COM1
COM2
9E
RS485
RS485
9G
10Base-F and 10Base-T
RS485
9H
Redundant 10Base-F
RS485
9J
100Base-FX
RS485
9K
Redundant 100Base-FX
RS485
9L
100Base-FX
RS485
9M
Redundant 100Base-FX
RS485
9N
10/100Base-T
RS485
9P
100Base-FX
RS485
9R
Redundant 100Base-FX
RS485
9S
Ethernet switch module with two 10/100Base-T and four 100Base-FX ports
RS485
NOTE
NOTE
Содержание G60 UR Series
Страница 2: ......
Страница 4: ......
Страница 12: ...xii G60 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Страница 32: ...1 20 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 102: ...3 48 G60 Generator Protection System GE Multilin 3 4 MANAGED ETHERNET SWITCH MODULES 3 HARDWARE 3 ...
Страница 132: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 392: ...5 260 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 418: ...6 26 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 446: ...8 18 G60 Generator Protection System GE Multilin 8 3 ENERVISTA SECURITY MANAGEMENT SYSTEM 8 SECURITY 8 ...
Страница 452: ...9 6 G60 Generator Protection System GE Multilin 9 1 PHASE DISTANCE THROUGH POWER TRANSFORMERS 9 THEORY OF OPERATION 9 ...
Страница 482: ...A 12 G60 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIXA A ...
Страница 604: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Страница 616: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Страница 634: ...x G60 Generator Protection System GE Multilin INDEX ...