GE Multilin
G60 Generator Protection System
10-13
10 APPLICATION OF SETTINGS
10.1 SETTING EXAMPLE
10
10.1.16 FLEXLOGIC™
The following logic as given as an example only. The logic for each specific application will be dependant on system design,
protection philosophies, and operating practices.
Figure 10–5: APPLICATION EXAMPLE FLEXLOGIC™
STATOR GND STG1 OP
29
30
OR(6)
31
= TURBINE TRIP (VO3)
32
58
END
PHASE TOC1 OP
GEN UNBAL STG1 OP
3
4
SEQ TRIP ON (VO9)
STATOR DIFF OP
1
2
OR(11)
= GEN BKR TRIP (VO1)
OVEREXCIT ON (VO7)
UNDERFREQ ON (VO5)
7
8
LOSS EXCIT OP
DIR POWER 1 STG 1 OP
5
6
ACCDNT ENRG OP
OR(11)
11
12
AUX OV1 OP
STATOR GND STG1 OP
9
10
= GEN BKR TRIP (VO1)
13
LOSS EXCIT OP
DIR POWER STG1 OP
16
17
SEQ TRIP ON (VO9)
STATOR DIFF OP
14
15
OR(7)
= FLD BKR TRIP (VO2)
STATOR GND STG1 OP
OR(7)
20
21
OVEREXCIT ON (VO7)
AUX OV1 OP
18
19
= FLD BKR TRIP (VO2)
22
DIR POWER 1 STG1 OP
ONLINE ON (VO8)
25
26
STATOR DIFF OP
LOSS EXCIT OP
23
24
OR(6)
= TURBINE TRIP (VO3)
AUX OV1 OP
OVEREXCIT ON (VO7)
AND(2)
27
28
AND(2)
35
36
33
34
39
37
38
GEN UNBAL STG2 OP
OVERFREQ ON (VO6)
VOLTS PER HERTZ 1 PKP
TIMER 1
OR(4)
= ALARM (VO4)
= ALARM (VO4)
STATOR GND STG2 OP
OR(4)
5 sec.
0 sec.
42
43
40
41
OR(2)
= UNDERFREQ (VO5)
UNDERFREQ 1 OP
UNDERFREQ 2 OP
OR(2)
= UNDERFREQ (VO5)
46
47
44
45
OR(2)
= OVERFREQ (VO6)
OVERFREQ 1 OP
OVERFREQ 2 OP
OR(2)
= OVERFREQ (VO6)
50
51
48
49
OR(2)
= OVEREXCIT (VO7)
VOLTS PER HERTZ 1 OP
VOLTS PER HERTZ 2 OP
OR(2)
= OVEREXCIT (VO7)
52
53
OFFLINE OFF(H7C)
= ONLINE (VO8)
= ONLINE (VO8)
56
57
54
55
AND(2)
= SEQ TRIP (VO9)
DIR POWER 1 STG2 OP
INLET VALVE OFF(H8A)
AND(2)
= SEQ TRIP (VO9)
830732A1.CDR
Содержание G60 UR Series
Страница 2: ......
Страница 4: ......
Страница 12: ...xii G60 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Страница 32: ...1 20 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 102: ...3 48 G60 Generator Protection System GE Multilin 3 4 MANAGED ETHERNET SWITCH MODULES 3 HARDWARE 3 ...
Страница 132: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 392: ...5 260 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 418: ...6 26 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 446: ...8 18 G60 Generator Protection System GE Multilin 8 3 ENERVISTA SECURITY MANAGEMENT SYSTEM 8 SECURITY 8 ...
Страница 452: ...9 6 G60 Generator Protection System GE Multilin 9 1 PHASE DISTANCE THROUGH POWER TRANSFORMERS 9 THEORY OF OPERATION 9 ...
Страница 482: ...A 12 G60 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIXA A ...
Страница 604: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Страница 616: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Страница 634: ...x G60 Generator Protection System GE Multilin INDEX ...