GE Multilin
G60 Generator Protection System
5-23
5 SETTINGS
5.2 PRODUCT SETUP
5
PATH: SETTINGS
Ö
PRODUCT SETUP
ÖØ
COMMUNICATIONS
ÖØ
IEC 61850 PROTOCOL
Ö
GSSE/GOOSE...
Ö
TRANSMISSION
The general transmission settings are shown below:
PATH: SETTINGS
Ö
PRODUCT SETUP
ÖØ
COMMUNICATIONS
ÖØ
IEC 61850...
Ö
GSSE/GOOSE...
Ö
TRANSMISSION
Ö
GENERAL
The
DEFAULT GSSE/GOOSE UPDATE TIME
sets the time between GSSE or GOOSE messages when there are no remote out-
put state changes to be sent. When remote output data changes, GSSE or GOOSE messages are sent immediately. This
setting controls the steady-state
heartbeat
time interval.
The
DEFAULT GSSE/GOOSE UPDATE TIME
setting is applicable to GSSE, fixed G60 GOOSE, and configurable GOOSE.
The GSSE settings are shown below:
PATH: SETTINGS
Ö
PRODUCT SETUP
ÖØ
COMMUNICATIONS
ÖØ
IEC 61850...
Ö
GSSE/GOOSE...
Ö
TRANSMISSION
ÖØ
GSEE
These settings are applicable to GSSE only. If the fixed GOOSE function is enabled, GSSE messages are not transmitted.
The
GSSE ID
setting represents the IEC 61850 GSSE application ID name string sent as part of each GSSE message. This
string identifies the GSSE message to the receiving device. In G60 releases previous to 5.0x, this name string was repre-
sented by the
RELAY NAME
setting.
The fixed GOOSE settings are shown below:
PATH: SETTINGS
Ö
PRODUCT...
ÖØ
COMMUNICATIONS
ÖØ
IEC 61850...
Ö
GSSE/GOOSE...
Ö
TRANSMISSION
ÖØ
FIXED GOOSE
TRANSMISSION
GENERAL
MESSAGE
GSSE
MESSAGE
FIXED GOOSE
MESSAGE
CONFIGURABLE
GOOSE
GENERAL
DEFAULT GSSE/GOOSE
UPDATE TIME: 60 s
Range: 1 to 60 s in steps of 1
GSSE
GSSE FUNCTION:
Enabled
Range: Enabled, Disabled
MESSAGE
GSSE ID:
GSSEOut
Range: 65-character ASCII string
MESSAGE
DESTINATION MAC:
000000000000
Range: standard MAC address
FIXED GOOSE
GOOSE FUNCTION:
Disabled
Range: Enabled, Disabled
MESSAGE
GOOSE ID:
GOOSEOut
Range: 65-character ASCII string
MESSAGE
DESTINATION MAC:
000000000000
Range: standard MAC address
MESSAGE
GOOSE VLAN PRIORITY:
4
Range: 0 to 7 in steps of 1
MESSAGE
GOOSE VLAN ID:
0
Range: 0 to 4095 in steps of 1
MESSAGE
GOOSE ETYPE APPID:
0
Range: 0 to 16383 in steps of 1
Содержание G60 UR Series
Страница 2: ......
Страница 4: ......
Страница 12: ...xii G60 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Страница 32: ...1 20 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 102: ...3 48 G60 Generator Protection System GE Multilin 3 4 MANAGED ETHERNET SWITCH MODULES 3 HARDWARE 3 ...
Страница 132: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 392: ...5 260 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 418: ...6 26 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 446: ...8 18 G60 Generator Protection System GE Multilin 8 3 ENERVISTA SECURITY MANAGEMENT SYSTEM 8 SECURITY 8 ...
Страница 452: ...9 6 G60 Generator Protection System GE Multilin 9 1 PHASE DISTANCE THROUGH POWER TRANSFORMERS 9 THEORY OF OPERATION 9 ...
Страница 482: ...A 12 G60 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIXA A ...
Страница 604: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Страница 616: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Страница 634: ...x G60 Generator Protection System GE Multilin INDEX ...