G60 Generator Protection System
GE Multilin
10.1 SETTING EXAMPLE
10 APPLICATION OF SETTINGS
10
10.1.12 OVEREXCITATION
This protection should be set to coordinate with the manufacturers excitation capability curves. For example system, the
combined generator/GSU limit curve is shown below:
Figure 10–4: GENERATOR/GSU LIMIT CURVE
Program the volts per hertz 1 element with an inverse characteristic (curve A), a pickup of 1.05, and a TDM of 40. Program
the volts per hertz 2 element with a definite time characteristic, a pickup of 1.23, and a time delay of 2 seconds. Both ele-
ments will issue a trip. The volts per hertz 1 pickup will be used to generate an alarm. Either source may be assigned in this
example. Make the following changes in EnerVista UR Setup or through the
SETTINGS
ÖØ
GROUPED ELEMENTS
ÖØ
SET-
TING GROUP 1
ÖØ
VOLTAGE ELEMENTS
Ö
VOLTS/HZ 1(2)
menus:
Volts per hertz (p.u.)
Combined generator/GSU
limit curve
Volts per
hertz 1
Volts per
hertz 2
Time
(seconds)
830734A1.CDR
Содержание G60 UR Series
Страница 2: ......
Страница 4: ......
Страница 12: ...xii G60 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Страница 32: ...1 20 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 102: ...3 48 G60 Generator Protection System GE Multilin 3 4 MANAGED ETHERNET SWITCH MODULES 3 HARDWARE 3 ...
Страница 132: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 392: ...5 260 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 418: ...6 26 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 446: ...8 18 G60 Generator Protection System GE Multilin 8 3 ENERVISTA SECURITY MANAGEMENT SYSTEM 8 SECURITY 8 ...
Страница 452: ...9 6 G60 Generator Protection System GE Multilin 9 1 PHASE DISTANCE THROUGH POWER TRANSFORMERS 9 THEORY OF OPERATION 9 ...
Страница 482: ...A 12 G60 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIXA A ...
Страница 604: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Страница 616: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Страница 634: ...x G60 Generator Protection System GE Multilin INDEX ...