GE Multilin
G60 Generator Protection System
2-13
2 PRODUCT DESCRIPTION
2.2 SPECIFICATIONS
2
RATE OF CHANGE OF FREQUENCY
df/dt trend:
increasing, decreasing, bi-directional
df/dt pickup level:
0.10 to 15.00 Hz/s in steps of 0.01
df/dt dropout level:
96% of pickup
df/dt level accuracy:
80 mHz/s or 3.5%, whichever is greater
Overvoltage supv.:
0.100 to 3.000 pu in steps of 0.001
Overcurrent supv.:
0.000 to 30.000 pu in steps of 0.001
Pickup delay:
0 to 65.535 s in steps of 0.001
Reset delay:
0 to 65.535 s in steps of 0.001
Time accuracy:
±3% or ±4 ms, whichever is greater
95% settling time for df/dt: < 24 cycles
Operate time:
typically 6.5 cycles at 2
×
pickup
typically 5.5 cycles at 3
×
pickup
typically 4.5 cycles at 5
×
pickup
TURBINE FREQUENCY OUT-OF-BAND (OOB)
ACCUMULATED OPERATING TIME
Frequency OOB accumulation: 7 sets; 20 to 70 Hz in steps of 0.01
Frequency OOB accumulation pickup: 1 to 65536 s in steps of 1
Frequency OOB accumulator preset: 1 to 65536 s in steps of 1
Level accuracy:
±0.01 Hz
Minimum volt/amp supervision: 0.1 to 1.25 pu of V_1 or I_1
Timing accuracy of accumulation: ±1% or 1 second, whichever is
greater
SYNCHROCHECK
Max voltage difference:
0 to 400000 V in steps of 1
Max angle difference:
0 to 100
°
in steps of 1
Max freq. difference:
0.00 to 2.00 Hz in steps of 0.01
Hysteresis for max. freq. diff.: 0.00 to 0.10 Hz in steps of 0.01
Dead source function:
None, LV1 & DV2, DV1 & LV2, DV1 or
DV2, DV1 xor DV2, DV1 & DV2
(L = Live, D = Dead)
POWER SWING DETECT
Functions:
Power swing block, Out-of-step trip
Characteristic:
Mho or Quad
Measured impedance:
Positive-sequence
Blocking / tripping modes: 2-step or 3-step
Tripping mode:
Early or Delayed
Current supervision:
Pickup level:
0.050 to 30.000 pu in steps of 0.001
Dropout level:
97 to 98% of pickup
Fwd / reverse reach (sec.
Ω
): 0.10 to 500.00
Ω
in steps of 0.01
Left and right blinders (sec.
Ω
): 0.10 to 500.00
Ω
in steps of 0.01
Impedance accuracy:
±5%
Fwd / reverse angle impedances: 40 to 90° in steps of 1
Angle accuracy:
±2°
Characteristic limit angles: 40 to 140° in steps of 1
Timers:
0.000 to 65.535 s in steps of 0.001
Timing accuracy:
±3% or 4 ms, whichever is greater
ACCIDENTAL ENERGIZATION
Operating condition:
Overcurrent
Arming condition:
Undervoltage and/or Machine Offline
Overcurrent:
Pickup level:
0.000 to 3.000 pu in steps of 0.001
Dropout level:
97 to 98% of pickup
Level accuracy:
±0.5% of reading from
0.1 to 2.0
×
CT rating
Undervoltage:
Pickup level:
0.000 to 3.000 pu in steps of 0.001
Dropout level:
102 to 103% of pickup
Level accuracy:
±0.5% of reading 10 to 208 V
Operate Time:
< 30 ms at 1.10
×
pickup at 60 Hz
LOSS OF EXCITATION
Operating condition:
Positive-sequence impedance
Characteristic:
2 independent offset mho circles
Center:
0.10 to 300.0
Ω
(sec.) in steps of 0.01
Radius:
0.10 to 300.0
Ω
(sec.) in steps of 0.01
Reach accuracy:
±3%
Undervoltage supervision
Level:
0.000 to 1.250 pu in steps of 0.001
Accuracy:
±0.5% of reading from 10 to 208 V
Pickup delay:
0 to 65.535 s in steps of 0.001
Timing accuracy:
±3% or ±20 ms, whichever is greater
Operate time:
<50 ms
RTD PROTECTION
Pickup:
1 to 249°C in steps of 1
Dropout level:
2°C of pickup
Timing accuracy:
<1 s
Elements:
trip and alarm
REMOTE RTD PROTECTION
Pickup level:
1 to 200°C
Dropout level:
2°C of pickup
Time delay:
<10 s
Elements:
trip and alarm
TRIP BUS (TRIP WITHOUT FLEXLOGIC™)
Number of elements:
6
Number of inputs:
16
Operate time:
<2 ms at 60 Hz
Time accuracy:
±3% or 10 ms, whichever is greater
Содержание G60 UR Series
Страница 2: ......
Страница 4: ......
Страница 12: ...xii G60 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Страница 32: ...1 20 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 102: ...3 48 G60 Generator Protection System GE Multilin 3 4 MANAGED ETHERNET SWITCH MODULES 3 HARDWARE 3 ...
Страница 132: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 392: ...5 260 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 418: ...6 26 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 446: ...8 18 G60 Generator Protection System GE Multilin 8 3 ENERVISTA SECURITY MANAGEMENT SYSTEM 8 SECURITY 8 ...
Страница 452: ...9 6 G60 Generator Protection System GE Multilin 9 1 PHASE DISTANCE THROUGH POWER TRANSFORMERS 9 THEORY OF OPERATION 9 ...
Страница 482: ...A 12 G60 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIXA A ...
Страница 604: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Страница 616: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Страница 634: ...x G60 Generator Protection System GE Multilin INDEX ...