AO-54 Terminal X42/9 Timeout Preset
Range:
Function:
0 %
*
[0 -
100 %]
Holds the preset level of terminal X42/9.
If a fieldbus and a time-out function are
selected in
parameter AO-60 Terminal X42/11
, the output presets to this level.
3.10.7 AO-6# Analog Out X42/11
AO-60 Terminal X42/11 Output
Option:
Function:
Set the function of terminal X42/11.
[0]
*
No operation
[100] Output
frequency
0–100 Hz, (0–10 V).
[101] Reference
Minimum reference–maximum reference,
(0–10 V).
[102] Feedback
-200% to +200% of
parameter F-53 Maximum Reference
, (0–10
V).
[103] Motor Current
0–inverter maximum current
(
parameter DR-37 Drive Max. Current
), (0–
10 V).
[104] Torque rel to
limit
0–torque limit (
), (0–10 V).
[105] Torq relate to
rated
0–motor rated torque, (0–0 V).
[106] Power
0–motor rated power, (0–10 V).
[107] Speed
0–speed high limit (
parameter F-15 Motor Speed High Limit
), (0–10 V).
[113] Ext. Closed
Loop 1
0–100%, (0–10 V).
[114] Ext. Closed
Loop 2
0–100%, (0–10 V).
[115] Ext. Closed
Loop 3
0–100%, (0–10 V).
[139] Bus ctrl.
0–100%, (0–10 V).
[141] Bus ctrl t.o.
0–100%, (0–10 V).
AO-61 Terminal X42/11 Min. Scale
For more information, see
parameter AN-51 Terminal 42 Output
.
Range:
Function:
0 %
*
[0 -
200 %]
Scale the minimum output of the selected
analog signal at terminal X42/11, as a
percentage of the maximum signal level. For
example, if 0 V is required at 25% of the
maximum output value, program 25%. Scaling
values up to 100% can never be higher than
AO-61 Terminal X42/11 Min. Scale
parameter AN-51 Terminal 42 Output
.
Range:
Function:
parameter AO-62 Terminal X42/11 Max. Scale
AO-62 Terminal X42/11 Max. Scale
See
.
Range:
Function:
100
%
*
[0 -
200 %]
Scale the maximum output of the selected
analog signal at terminal X42/9. Set the value to
the maximum value of the voltage signal output.
Scale the output to give a voltage lower than 10
V at full scale; or 10 V at an output below 100%
of the maximum signal value. For example, If 10
V is the required output current at a value
between 0–100% of the full-scale output,
program the percentage value in the parameter,
that is, 50%=10 V. If a voltage between 0 and 10
V is required at maximum output, calculate the
percentage as follows:
10
V
desired
maximum
voltage x
100 %
that is
5
V
:
10
V
5
V x
100 % = 200 %
AO-63 Terminal X42/11 Bus Control
Range:
Function:
0 %
*
[0 - 100 %] Holds the level of terminal X42/11 if
controlled by bus.
AO-64 Terminal X42/11 Timeout Preset
Range:
Function:
0 %
*
[0 - 100 %] Holds the preset level of terminal X42/11.
If a fieldbus and a time-out function are
selected, the output presets to this level.