3.2 F-##
Fundamental
Parameters
3.2.1 F-0# Fundamental Parameters
F-01 Frequency Setting 1
Option:
Function:
NOTICE
This parameter cannot be adjusted
while the motor is running.
Select the reference input to be used for
the 1
st
reference signal:
•
Parameter F-01 Frequency Setting
.
•
•
Define up to 3 different reference signals.
The sum of these reference signals defines
the actual reference.
[0]
No function
[1]
*
Analog Input
53
[2]
Analog Input
54
[7]
Pulse input 29
[8]
Pulse input 33
[20]
Digital Potenti-
ometer
[21]
Analog input
X30/11
(OPCGPIO)
[22]
Analog input
X30/12
(OPCGPIO)
[23]
Analog Input
X42/1
(OPCAIO)
[24]
Analog Input
X42/3
(OPCAIO)
[25]
Analog Input
X42/5
(OPCAIO)
[30]
Ext. Closed
Loop 1
[31]
Ext. Closed
Loop 2
[32]
Ext. Closed
Loop 3
F-02 Operation Method
Option:
Function:
Select which reference site to activate.
[0]
*
Linked to
Hand / Auto
Use local reference when in hand-on mode,
or remote reference when in auto-on mode.
F-02 Operation Method
Option:
Function:
[1]
Remote
Use remote reference in both hand-on mode
and auto-on mode.
[2]
Local
Use local reference in both hand-on mode
and auto-on mode.
NOTICE
When set to
[2] Local
, the frequency
converter starts with this setting again
after a power-down.
F-03 Max Output Frequency 1
Range:
Function:
100.0
Hz
*
[1 -
590
Hz]
NOTICE
This parameter cannot be adjusted while
the motor is running.
Enter the maximum output frequency value.
Parameter F-03 Max Output Frequency 1
specifies
the absolute limit on the frequency converter
output frequency for improved safety in
applications where accidental over-speeding
must be avoided. This absolute limit applies to
all configurations and is independent of the
setting in
parameter H-40 Configuration Mode
When
parameter P-20 Motor Construction
is set
to
[1] PM non-salient SPM
, the maximum value is
limited to 300 Hz.
F-04 Base Frequency
Range:
Function:
50 Hz
*
[20 - 1000 Hz]
NOTICE
This parameter cannot be adjusted
while the motor is running.
Select the motor frequency value from
the motor nameplate data.
F-05 Motor Rated Voltage
Range:
Function:
400 V
*
[10 - 1000
V]
NOTICE
This parameter cannot be adjusted
while the motor is running.
Enter the nominal motor voltage according
to the motor nameplate data. The default
value corresponds to the nominal rated
output of the frequency converter.
Parameter Description
AF-600 FP
™
Programming Guide
DET-620D
03/2016 All rights reserved.
35
3