XC-13 Ext. 1 Reference Source
Option:
Function:
This parameter defines which input
on the frequency converter that
should be treated as the source of
the reference signal for the closed
loop 1 controller. Analog input
X30/11 and analog input X30/12
refer to inputs on the General
Purpose I/O Card OPCGPIO General
Purpose I/O.
[0]
*
No function
[1]
Analog Input 53
[2]
Analog Input 54
[7]
Pulse input 29
[8]
Pulse input 33
[20]
Digital Potentiometer
[21]
Analog input X30/11
[22]
Analog input X30/12
[23]
Analog Input X42/1
[24]
Analog Input X42/3
[25]
Analog Input X42/5
[30]
Ext. Closed Loop 1
[31]
Ext. Closed Loop 2
[32]
Ext. Closed Loop 3
XC-14 Ext. 1 Feedback Source
Option:
Function:
This parameter defines which input
on the frequency converter should
be treated as the source of the
feedback signal for the closed-loop 1
controller. Analog input X30/11 and
analog input X30/12 refer to inputs
on the General Purpose I/O Card
OPCGPIO General Purpose I/O.
[0]
*
No function
[1]
Analog Input 53
[2]
Analog Input 54
[3]
Pulse input 29
[4]
Pulse input 33
[7]
Analog Input X30/11
[8]
Analog Input X30/12
[9]
Analog Input X42/1
[10]
Analog Input X42/3
[11]
Analog Input X42/5
[100] Bus Feedback 1
[101] Bus Feedback 2
[102] Bus feedback 3
XC-15 Ext. 1 Setpoint
Range:
Function:
0
ExtPID1Unit
*
[par. XC-11 -
par. XC-12
ExtPID1Unit]
The setpoint reference is used
in extended 1 closed loop. Ext.1
setpoint is added to the value
from the Ext.1 Reference source
selected in
XC-17 Ext. 1 Reference [Unit]
Range:
Function:
0 ExtPID1Unit
*
[-999999.999 -
999999.999
ExtPID1Unit]
Readout of the reference
value for the closed-loop
1 controller.
XC-18 Ext. 1 Feedback [Unit]
Range:
Function:
0 ExtPID1Unit
*
[-999999.999 -
999999.999
ExtPID1Unit]
Readout of the feedback
value for the closed-loop
1 controller.
XC-19 Ext. 1 Output [%]
Range:
Function:
0 %
*
[0 - 100 %] Readout of the output value for the closed-
loop 1 controller.
3.23.3 XC-2# Ext. CL 1 PID
XC-20 Ext. 1 Normal/Inverse Control
Option:
Function:
[0]
*
Normal Reduces the output when feedback is higher than
the reference.
[1]
Inverse Increase the output when feedback is higher than
the reference.
XC-21 Ext. 1 Proportional Gain
Range:
Function:
0.01
*
[0 -
10]
NOTICE
before setting the values
for the PID controller in parameter group
CL-9#
.
The proportional gain indicates the number of
times the error between the setpoint and the
feedback signal is to be applied.
If (error x gain) jumps with a value equal to what is set in
parameter CL-14 Maximum Reference/Feedb.
, the PID
controller tries to change the output speed equal to what
is set in
parameter F-17 Motor Speed High Limit [RPM]
parameter F-15 Motor Speed High Limit [Hz]
. However, the
output speed is limited by this setting.
Parameter Description
168
03/2016 All rights reserved.
DET-620D
3
3