Par. No. #
Parameter description
Default value
4-set-up
Change
during
operation
Conver-
sion index
Type
CL-20
Feedback Function
[3] Minimum
All set-ups
TRUE
-
Uint8
CL-21
Setpoint 1
0 ProcessCtrlUnit
All set-ups
TRUE
-3
Int32
CL-22
Setpoint 2
0 ProcessCtrlUnit
All set-ups
TRUE
-3
Int32
CL-23
Setpoint 3
0 ProcessCtrlUnit
All set-ups
TRUE
-3
Int32
CL-3#
CL-30
Refrigerant
[0] R22
All set-ups
TRUE
-
Uint8
CL-31
User Defined Refrigerant A1
10 N/A
All set-ups
TRUE
-4
Uint32
CL-32
User Defined Refrigerant A2
-2250 N/A
All set-ups
TRUE
-2
Int32
CL-33
User Defined Refrigerant A3
250 N/A
All set-ups
TRUE
-3
Uint32
CL-34
Duct 1 Area [m2]
0.500 m2
All set-ups
TRUE
-3
Uint32
CL-35
Duct 1 Area [in2]
750 in2
All set-ups
TRUE
0
Uint32
CL-36
Duct 2 Area [m2]
0.500 m2
All set-ups
TRUE
-3
Uint32
CL-37
Duct 2 Area [in2]
750 in2
All set-ups
TRUE
0
Uint32
CL-38
Air Density Factor [%]
100 %
All set-ups
TRUE
0
Uint32
CL-7#
CL-70
Closed Loop Type
[0] Auto
2 set-ups
TRUE
-
Uint8
CL-71
PID Performance
[0] Normal
2 set-ups
TRUE
-
Uint8
CL-72
PID Output Change
0.10 N/A
2 set-ups
TRUE
-2
Uint16
CL-73
Minimum Feedback Level
-999999 ProcessCtrlUnit
2 set-ups
TRUE
-3
Int32
CL-74
Maximum Feedback Level
999999 ProcessCtrlUnit
2 set-ups
TRUE
-3
Int32
CL-79
PID Autotuning
[0] Disabled
All set-ups
TRUE
-
Uint8
CL-8#
CL-81
PID Normal/ Inverse Control
[0] Normal
All set-ups
TRUE
-
Uint8
CL-82
PID Start Speed [RPM]
ExpressionLimit
All set-ups
TRUE
67
Uint16
CL-83
PID Start Speed [Hz]
ExpressionLimit
All set-ups
TRUE
-1
Uint16
CL-84
On Reference Bandwidth
5 %
All set-ups
TRUE
0
Uint8
CL-9#
CL-91
PID Anti Windup
[1] On
All set-ups
TRUE
-
Uint8
CL-93
PID Proportional Gain
0.50 N/A
All set-ups
TRUE
-2
Uint16
CL-94
PID Integral Time
20 s
All set-ups
TRUE
-2
Uint32
CL-95
PID Differentiation Time
0 s
All set-ups
TRUE
-2
Uint16
CL-96
PID Diff. Gain Limit
5 N/A
All set-ups
TRUE
-1
Uint16
5.1.24 XC-## Ext. PID Closed Loop
Par. No. #
Parameter description
Default value
4-set-up
Change
during
operation
Conver-
sion index
Type
XC-0#
XC-00
Closed Loop Type
[0] Auto
2 set-ups
TRUE
-
Uint8
XC-01
PID Performance
[0] Normal
2 set-ups
TRUE
-
Uint8
XC-02
PID Output Change
0.10 N/A
2 set-ups
TRUE
-2
Uint16
XC-03
Minimum Feedback Level
-999999 N/A
2 set-ups
TRUE
-3
Int32
XC-04
Maximum Feedback Level
999999 N/A
2 set-ups
TRUE
-3
Int32
XC-09
PID Autotuning
[0] Disabled
All set-ups
TRUE
-
Uint8
XC-1#
XC-10
Ext. 1 Ref./Feedback Unit
[1] %
All set-ups
TRUE
-
Uint8
XC-11
Ext. 1 Minimum Reference
0 ExtPID1Unit
All set-ups
TRUE
-3
Int32
XC-12
Ext. 1 Maximum Reference
100 ExtPID1Unit
All set-ups
TRUE
-3
Int32
XC-13
Ext. 1 Reference Source
[0] No function
All set-ups
TRUE
-
Uint8
XC-14
Ext. 1 Feedback Source
[0] No function
All set-ups
TRUE
-
Uint8
Parameter Lists
230
03/2016 All rights reserved.
DET-620D
5
5