3.7.7 AN-5# Analog Output 1
Parameters for configuring the scaling and limits for analog
output 1, that is terminal 42. Analog outputs are current
outputs: 0/4–20 mA. Common terminal (terminal 39) is the
same terminal and has the same electrical potential for
analog common and digital common connection.
Resolution on analog output is 12 bit.
AN-50 Terminal 42 Output
Option:
Function:
NOTICE
Values for setting the minimum
reference are found in open loop
parameter F-52 Minimum Reference
and for closed loop
parameter CL-13 Minimum
Reference/Feedb.
. Values for
maximum reference for open loop
are found in
parameter F-53 Maximum Reference
and for closed loop
parameter CL-14 Maximum
Reference/Feedb.
This parameter enables the function of
terminal 42 as an analog current output.
Depending on the option selected, the
output is either 0–20 mA or 4–20 mA.
The current value can be read out in the
parameter DR-65 Analog Output 42
[0]
No operation
[100]
Output
frequency
0–100 Hz, (0–20 mA).
[101]
Reference
Minimum reference–Maximum reference,
(0–20 mA).
[102]
Feedback
parameter CL-14 Maximum Reference/
, (0–20 mA).
[103]
Motor Current
0–Inverter maximum current
(
parameter DR-37 Drive Max. Current
),
(0-20 mA).
[104]
Torque rel to
limit
0–Torque limit (
), (0–20 mA).
[105]
Torq relate to
rated
0–Motor rated torque, (0–20 mA).
[106]
Power
0–Motor rated power, (0–20 mA).
[107]
Speed
0–Speed high limit (
and
parameter F-15 Motor Speed High Limit
), (0–20 mA).
[113]
Ext. Closed
Loop 1
0–100%, (0–20 mA).
AN-50 Terminal 42 Output
Option:
Function:
[114]
Ext. Closed
Loop 2
0–100%, (0–20 mA).
[115]
Ext. Closed
Loop 3
0–100%, (0–20 mA).
[117]
Shaft Power
[118]
Shaft Power
4-20mA
[130]
Output freq.
4-20mA
0–100 Hz.
[131]
Reference
4-20mA
Minimum reference–Maximum reference.
[132]
Feedback
4-20mA
-200% to +200% of
parameter CL-14 Maximum Reference/
[133]
Motor cur.
4-20mA
0–Inverter maximum current
(
parameter DR-37 Drive Max. Current
[134]
Torq.% lim
4-20 mA
0–Torque limit (
[135]
Torq.% nom
4-20mA
0–Motor rated torque.
[136]
Power 4-20mA 0–Motor rated power.
[137]
*
Speed 4-20mA 0–Speed high limit (F-18 and F-15).
[139]
Bus ctrl.
0–100%, (0–20 mA).
[140]
Bus ctrl. 4-20
mA
0–100%.
[141]
Bus ctrl t.o.
0–100%, (0–20 mA).
[142]
Bus ctrl t.o.
4-20mA
0–100%.
[143]
Ext. CL 1
4-20mA
0–100%.
[144]
Ext. CL 2
4-20mA
0–100%.
[145]
Ext. CL 3
4-20mA
0–100%.
[184]
Mirror AI53
mA
[185]
Mirror AI54
mA
AN-51 Terminal 42 Output Min Scale
Range:
Function:
0 %
*
[0 -
200 %]
Scale for the minimum output (0 mA or 4 mA)
of the analog signal at terminal 42.
Set the value to be the percentage of the full
range of the variable selected in
parameter AN-50 Terminal 42 Output
Parameter Description
AF-600 FP
™
Programming Guide
DET-620D
03/2016 All rights reserved.
73