F-12 Motor Thermistor Input
Option:
Function:
NOTICE
This parameter cannot be adjusted
while the motor is running.
NOTICE
Set digital input to
[0] PNP - Active at
24 V
in E-0#.
Select the input to which the thermistor (PTC
sensor) should be connected. An analog
input option
[1] Analog Input 53
or
[2] Analog
Input 54
cannot be selected if the analog
input is already in use as a reference source
(selected in
parameter F-01 Frequency Setting
,
parameter C-30 Frequency Command 2
or
parameter C-34 Frequency Command 3
[0]
*
None
[1]
Analog Input
53
[2]
Analog Input
54
[3]
Digital input
18
[4]
Digital input
19
[5]
Digital input
32
[6]
Digital input
33
F-15 Motor Speed High Limit [Hz]
Range:
Function:
50.0 Hz
*
[par. F-16 - par. F-03 Hz]
F-16 Motor Speed Low Limit [Hz]
Range:
Function:
0 Hz
*
[0 - par.
F-15 Hz]
Enter the minimum limit for motor speed in
Hz. The motor speed low limit can be set to
correspond to the minimum output frequency
of the motor shaft. The speed low limit must
not exceed the setting in
F-17 Motor Speed High Limit [RPM]
Range:
Function:
1500
RPM
*
[par.
F-18 -
60000
RPM]
NOTICE
Any changes in
reset the value
in
parameter H-73 Warning Speed High
to the value set in
.
F-17 Motor Speed High Limit [RPM]
Range:
Function:
NOTICE
Maximum output frequency cannot
exceed 10% of the carrier frequency
(
parameter F-26 Motor Noise (Carrier
).
Enter the maximum limit for motor speed in
RPM. The motor speed high limit can be set
to correspond to the manufacturer’s maximum
rated motor. The motor speed high limit must
exceed the setting in
. The parameter name
or
, depending on:
•
The settings of other parameters in
the
Main Menu
.
•
Default settings based on
geographical location.
F-18 Motor Speed Low Limit [RPM]
Range:
Function:
0 RPM
*
[0 - par.
F-17 RPM]
Enter the minimum limit for motor speed in
RPM. The motor speed low limit can be set
to correspond to the minimum motor speed
recommended by the manufacturer. The
motor speed low limit must not exceed the
setting in
parameter F-17 Motor Speed High
.
3.2.4 F-2# Fundamental Parameters 2
F-20 PM Start Mode
Option:
Function:
[0]
Rotor
Detection
Suitable for all applications where the motor is
known to be standing still when starting (for
example conveyors, pumps, and non-wind
milling fans).
[1]
*
Parking
If the motor turns at a low speed (that is
lower than 2–5% of the nominal speed), for
example due to fans with windmilling, select
[1] Parking
and adjust
and
accordingly.
Parameter Description
AF-600 FP
™
Programming Guide
DET-620D
03/2016 All rights reserved.
39
3
3