Illustration 3.20 Jog Ramp Time
C-23 Quick Stop Decel Time
Enter the quick stop ramp time. This is the acceleration/
deceleration time between 0 RPM and the rated motor frequency
in
. During ramping, the output current
must not exceed the current limit in
Range:
Function:
20.00 s
*
[1 - 3600 s]
3.4.3 C-3# Frequency Setting 2 and 3
C-30 Frequency Command 2
Option:
Function:
NOTICE
This parameter cannot be adjusted
while the motor is running.
Select the reference input to be used for
the 2
nd
reference signal:
•
Parameter F-01 Frequency Setting
.
•
•
Define up to 3 different reference signals.
The sum of these reference signals defines
the actual reference.
[0]
No function
[1]
Analog Input
53
[2]
Analog Input
54
[7]
Pulse input 29
[8]
Pulse input 33
[20]
*
Digital Potenti-
ometer
C-30 Frequency Command 2
Option:
Function:
[21]
Analog input
X30/11
(OPCGPIO)
[22]
Analog input
X30/12
(OPCGPIO)
[23]
Analog Input
X42/1
(OPCAIO)
[24]
Analog Input
X42/3
(OPCAIO)
[25]
Analog Input
X42/5
(OPCAIO)
[30]
Ext. Closed
Loop 1
[31]
Ext. Closed
Loop 2
[32]
Ext. Closed
Loop 3
C-34 Frequency Command 3
Option:
Function:
NOTICE
This parameter cannot be adjusted
while the motor is running.
Select the reference input to be used for
the 3
rd
reference signal:
•
Parameter F-01 Frequency Setting
.
•
•
Define up to 3 different reference signals.
The sum of these reference signals defines
the actual reference.
[0]
*
No function
[1]
Analog Input
53
[2]
Analog Input
54
[7]
Pulse input 29
[8]
Pulse input 33
[20]
Digital Potenti-
ometer
[21]
Analog input
X30/11
(OPCGPIO)
[22]
Analog input
X30/12
(OPCGPIO)
[23]
Analog Input
X42/1
(OPCAIO)
[24]
Analog Input
X42/3
(OPCAIO)
Parameter Description
AF-600 FP
™
Programming Guide