3.21 T-##
Timed
Functions
3.21.1 T-0# Timed actions
Use timed actions for actions performed on a daily or
weekly basis, for example different references for working
hours/non-working hours. Up to 10 timed actions can be
programmed in the frequency converter. The timed action
number is selected from the list when entering parameter
group
T-0#
from the keypad.
then refer to the selected timed
action number. Each timed action is divided into an ON
time and an OFF time, in which 2 different actions may be
performed.
Display lines 2 and 3 in the keypad show the status for
timed actions mode (
parameter K-23 Display Line 2 Large
and
parameter K-24 Display Line 3 Large
, setting
[1243]
Timed Actions Status
).
NOTICE
A change in mode via the digital inputs can only take
place if
parameter T-08 Timed Actions Mode
is set for
[0]
Times Actions Auto
.
If commands are applied simultaneously to the digital
inputs for constant OFF and constant ON, the timed
actions mode changes to timed actions auto and the 2
commands are disregarded.
If
is not set or the
frequency converter is set to
Hand
or
OFF
mode (for
Example via the keypad), the timed actions mode is
changed to
timed actions disabled
.
The timed actions have a higher priority than the same
actions/commands activated by the digital inputs or the
logic controller.
NOTICE
Programme the clock (parameter group
K-7#
) correctly
for timed actions to function.
NOTICE
When mounting Analog I/O Option OPCAIO, a battery
back-up of the date and time is included.
T-00 ON Time
Array [10]
Range:
Function:
0
*
[0 - 0] Sets the ON time for the timed action.
NOTICE
The frequency converter has no back-up of
the clock function and the set date/time
resets to default (2000-01-01 00:00) after a
power-down unless the Analog I/O option
module (OPCAIO) with Battery Back Up of
the Real Time Clock is installed. In
, it is possible to
programme a warning if the clock has not
been set properly, for example after a
power-down.
T-01 ON Action
Array [10]
Option:
Function:
Select the action during ON time.
See
parameter LC-52 Logic Controller
for descriptions of the
options.
[0]
*
Disabled
[1]
No action
[2]
Select set-up 1
[3]
Select set-up 2
[4]
Select set-up 3
[5]
Select set-up 4
[10]
Select preset ref 0
[11]
Select preset ref 1
[12]
Select preset ref 2
[13]
Select preset ref 3
[14]
Select preset ref 4
[15]
Select preset ref 5
[16]
Select preset ref 6
[17]
Select preset ref 7
[18]
Select Accel/Decel 1
[19]
Select Accel/Decel 2
[22]
Run
[23]
Run reverse
[24]
Stop
[26]
DC Brake
[27]
Coast
[32]
Set digital out A low
[33]
Set digital out B low
[34]
Set digital out C low
[35]
Set digital out D low
[36]
Set digital out E low
[37]
Set digital out F low
[38]
Set digital out A high
[39]
Set digital out B high
[40]
Set digital out C high