3.23.2 XC-1# Ext. CL 1 Ref./Fb.
Illustration 3.58 Closed Loop 1 Ref/Feedback
XC-10 Ext. 1 Ref./Feedback Unit
Option:
Function:
Select the unit for the reference and feedback.
[0]
[1]
*
%
[5]
PPM
[10]
1/min
[11]
RPM
[12]
Pulse/s
[20]
l/s
[21]
l/min
[22]
l/h
[23]
m3/s
[24]
m3/min
[25]
m3/h
[30]
kg/s
[31]
kg/min
[32]
kg/h
[33]
t/min
[34]
t/h
[40]
m/s
[41]
m/min
[45]
m
[60]
°C
[70]
mbar
[71]
bar
[72]
Pa
[73]
kPa
[74]
m WG
[75]
mm Hg
[80]
kW
[120]
GPM
XC-10 Ext. 1 Ref./Feedback Unit
Option:
Function:
[121]
gal/s
[122]
gal/min
[123]
gal/h
[124]
CFM
[125]
ft3/s
[126]
ft3/min
[127]
ft3/h
[130]
lb/s
[131]
lb/min
[132]
lb/h
[140]
ft/s
[141]
ft/min
[145]
ft
[160]
°F
[170]
psi
[171]
lb/in2
[172]
in WG
[173]
ft WG
[174]
in Hg
[180]
HP
XC-11 Ext. 1 Minimum Reference
Range:
Function:
0 ExtPID1Unit
*
[-999999.999 - par.
XC-12 ExtPID1Unit]
Select the minimum
reference for the closed-
loop 1 controller.
XC-12 Ext. 1 Maximum Reference
Range:
Function:
100
ExtPID1Unit
*
[par. XC-11 -
999999.999
ExtPID1Unit]
NOTICE
Set the value for
parameter XC-12 Ext. 1
Maximum Reference
before
setting the values for the
PID controller in parameter
group
CL-9#
.
Select the maximum reference for
the closed-loop 1 controller.
The dynamics of the PID
controller depend on the value
set in this parameter. See also
parameter XC-21 Ext. 1 Propor-
Parameter Description
AF-600 FP
™
Programming Guide
DET-620D
03/2016 All rights reserved.
167