FB-02 Fire Mode Unit
Option:
Function:
[31]
kg/min
[32]
kg/h
[33]
t/min
[34]
t/h
[40]
m/s
[41]
m/min
[45]
m
[60]
°C
[70]
mbar
[71]
bar
[72]
Pa
[73]
kPa
[74]
m WG
[75]
mm Hg
[80]
kW
[120] GPM
[121] gal/s
[122] gal/min
[123] gal/h
[124] CFM
[125] ft3/s
[126] ft3/min
[127] ft3/h
[130] lb/s
[131] lb/min
[132] lb/h
[140] ft/s
[141] ft/min
[145] ft
[160] °F
[170] psi
[171] lb/in2
[172] in WG
[173] ft WG
[174] in Hg
[180] HP
FB-03 Fire Mode Min Reference
Range:
Function:
0
FireMo-
deUnit
*
[-999999.999
- par. FB-04
FireModeUnit]
Minimum value for the reference/
setpoint (limiting the sum of value in
parameter FB-05 Fire Mode Preset
and value of signal on input
If running in open loop when fire
mode is active, the unit is selected by
the setting of
. For closed loop, select the
unit in
parameter FB-02 Fire Mode Unit
FB-04 Fire Mode Max Reference
Range:
Function:
50.000
FireMo-
deUnit
*
[par. FB-03 -
999999.999
FireModeUnit]
Maximum value for the reference/
setpoint (limiting the sum of value in
parameter FB-05 Fire Mode Preset
and value of signal on input
selected in
).
If running in open loop when fire
mode is active, the unit is selected by
the setting
. For closed loop, select the unit in
parameter FB-02 Fire Mode Unit
.
FB-05 Fire Mode Preset Reference
Range:
Function:
0 %
*
[-100 -
100 %]
Enter the required preset reference/set point as
a percentage of the Fire Mode Max Reference
set in
parameter FB-04 Fire Mode Max Reference
The set value is added to the value represented
by the signal on the analog input selected in
parameter FB-06 Fire Mode Reference Source
.
FB-06 Fire Mode Reference Source
Option:
Function:
Select the external reference input to
be used for the fire mode. This signal
is added to the value set in
parameter FB-06 Fire Mode Reference
[0]
*
No function
[1]
Analog Input 53
[2]
Analog Input 54
[7]
Pulse input 29
[8]
Pulse input 33
[20]
Digital Potentiometer
[21]
Analog input X30/11
(OPCGPIO)
[22]
Analog input X30/12
(OPCGPIO)
[23]
Analog Input X42/1
(OPCAIO)
[24]
Analog Input X42/3
(OPCAIO)
[25]
Analog Input X42/5
(OPCAIO)