O-05 End-of-Timeout Function
Option:
Function:
Select the action after receiving a valid control
word following a timeout.
This parameter is active only when
parameter O-04 Control Word Timeout Function
is
set to:
•
[7] Set-up 1
.
•
[8] Set-up 2
.
•
[9] Set-up 3
.
•
[10] Set-up 4
.
[0]
Hold set-
up
Retains the set-up selected in
parameter O-04 Control Word Timeout Function
toggles. Then the
frequency converter resumes its original set-up.
[1]
*
Resume
set-up
Resumes the set-up that was active before the
timeout.
O-06 Reset Control Word Timeout
Option:
Function:
This parameter is active only when option
[0] Hold
set-up
has been selected in
.
[0]
*
Do not
reset
Retains the set-up specified in
parameter O-04 Control Word Timeout Function
•
[7] Set-up 1
.
•
[8] Set-up 2
.
•
[9] Set-up 3
.
•
[10] Set-up 4
.
[1]
Do
reset
Returns the drive to the original set-up following a
control word timeout. When the value is set to
[1]
Do reset
, the drive performs the reset and
immediately reverts to the
[0] Do not reset
setting.
O-07 Diagnosis Trigger
Option:
Function:
To send no extended diagnosis data (EDD),
select
[0] Disable
. To send EDD upon alarms,.
select
[1] Trigger on alarms
. To send EDD
upon alarms or warnings, select
[2] Trigger
alarm/warn.
Not all fieldbusses support the
diagnosis functions.
[0]
*
Disable
[1]
Trigger on
alarms
[2]
Trigger
alarm/warn.
O-08 Readout Filtering
If the speed feedback value readouts on fieldbus are fluctuating,
this function is used. Select filtered, if the function is required. A
power cycle is required for changes to take effect.
Option:
Function:
[0]
*
Motor Data
Std-Filt.
Normal fieldbus readouts.
[1]
Motor Data
LP-Filter
Filtered fieldbus readouts of the following
parameters:
•
Parameter DR-10 Power [kW]
.
•
Parameter DR-11 Power [hp]
.
•
Parameter DR-12 Motor Voltage
.
•
Parameter DR-14 Motor current
.
•
Parameter DR-16 Torque [Nm]
.
•
Parameter DR-17 Speed [RPM]
.
•
Parameter DR-22 Torque [%]
.
•
Parameter DR-25 Torque [Nm] High
.
O-09 Communication Charset
Option:
Function:
[0]
ISO 8859-1
[1]
*
ANSI X3.4
[2]
UTF - 8
3.9.2 O-1# Control Settings
O-10 Control Word Profile
Option:
Function:
Select the interpretation of the control and
status words corresponding to the installed
network. Only the selections valid for the
network installed in slot A are visible in the
LPC display.
[0]
*
Drive Profile
[1]
PROFIdrive
profile
[5]
ODVA
Available only with DeviceNet MCA 104
and EtherNet IP .
O-13 Configurable Status Word STW
Array [16]
Option:
Function:
This parameter enables configuration of
bits 12–15 in the status word.
[0]
No function
[1]
*
Profile Default
The function corresponds to the profile
default selected in
[2]
Alarm 68 Only
Only set if
alarm 68, Safe stop
occurs.